030834b1a__specs_rohs, Basic unit, shelf, Mechanical – Alpha Technologies Cordex 48-1.2kW User Manual
Page 47: Connections, Safety

Specifications for Alpha Cordex 48-1.2kW 19" Front Access Shelf System
Alpha Technologies Ltd.
030-834-B1 Rev A
Printed in Canada. © 2010 Alpha Technologies Ltd. ALPHA and CORDEX are trademarks of Alpha Technologies Ltd. All Rights Reserved.
Basic Unit, Shelf
Maximum Output:
100A, 58Vdc
Recommended Feeder Breaker
Single Phase:
120V: 15A, #14 AWG (for two rectifiers)
220/240V: 20A, #12 AWG (for two rectifiers)
Mechanical
Dimensions:
88mm H x 439.5mm W x 305mm D (rectifier front panel 12.5mm D)
[3.5" H x 17.3" W x 12" D (rectifier front panel 0.49" D)]
Mounting*:
19" or 23" rack, 6" offset (center), EIA rack spacing
Weight:
4.55 kg (10.03 lb.)
Connections
AC Input (dual):
Dual IEC-60320-C20 MAIC connectors
(for use with IEC-60320-C19 female line cords)
Chassis ground:
#10-32 stud
Communications:
CAN (bus, single in/out) RJ-12 offset (female)
Site ground:
1/4" on 5/8" centers
Battery Output:
1/4" on 5/8" centers, two (2) sets per polarity
Load Output:
AM breakers: 1/4" on 5/8" centers
GMT fuses: screw terminal #16 to #26 AWG (1.5 to 0.129mm
2
)
Signal wiring:
Terminal blocks
#16 to #26 AWG (1.5 to 0.129mm
2
)
Safety
EN 60950
Rectifier output shall be rated SELV suitable for connection to TNV-1 circuits
UL
60950-1-2002
CSA
60950-1-03
CE
EN 60950, CB Scheme
73/23/EEC Low Voltage Directive with amendment 93/68/EEC
Telcordia (Bellcore)
NEBS certified Level 3 compliant
(meets all the requirements of GR-63-CORE and GR-1089-CORE)
NOTE: This equipment is suitable for use in “Common Bonding Network” configuration.
* See drawings at the rear of this manual.
The above information is valid at the time of publication. Consult factory for up-to-date ordering information.
Specifications are subject to change without notice.