Hardware specifications, cxcm1, Recommended signal wire sizes (as per ul/csa) – Alpha Technologies Cordex 48-1.2kW User Manual
Page 46

Specifications for Alpha CXCM1 Cordex Controller Continued
Alpha Technologies Ltd.
018-598-B1 Rev B
Printed in Canada. © 2010 Alpha Technologies Ltd. ALPHA and CORDEX are trademarks of Alpha Technologies Ltd. All Rights Reserved.
Page 2 of 2
Hardware Specifications, CXCM1
CPU:
Coldfire
RAM:
8MB
Flash:
4MB standard
Display:
4 digit LCD
Front Panel Controls:
Display pushbutton toggle switch for voltage (V) or current (A)
Reset switch (soft reset button; hold for 3 seconds to reset IP)
LED’s:
System OK (Green)
Power System Minor Alarm (Yellow)
Power System Major Alarm / Controller Fail (Red)
Audio:
Built-in speaker for alarm and popup message tones
Dimensions:
44mm H x 88mm W x 318mm D
[1.73" H x 3.5" W x 12.5" D]
Weight:
0.62 kg (1.36 lb.)
Mounting:
Modular on Cordex CXRF 48-1.2kW series shelves
[options for 1RU horizontal or 2RU vertical orientation depending on shelf]
Relay Outputs:
Four (4) Form C, 60Vdc 1A maximum
Digital Inputs:
Two (2), 0 to 60Vdc
Analog Inputs:
One (1) DC voltage, 0 to 60Vdc
One (1) DC current, ±50mV
Two (2) temperature, 0 to 20Vdc with power source
Communication Ports:
Ethernet RJ-45, Alpha Modem DB-9, CAN [see shelf specifications]
Recommended Signal Wire Sizes (as per UL/CSA)
Wire Size Range:
#16 to #26 AWG)
(1.5 to 0.14mm
2
)
Temperature Range:
0 to 50°C
(32 to 122°F)
CAUTION – TO REDUCE RISK OF FIRE, USE ONLY #26 AWG (0.14mm
2
) OR LARGER WIRE.
The above information is valid at the time of publication. Consult factory for up-to-date ordering information.
Specifications are subject to change without notice.