Setup

Setup can be performed using either a local user interface (LCD on the console) or a web interface (remotely connecting

with Tank Sentinel Anyware). In both of these cases, the sequence is the same. Refer to Chapter 6 - Level Probe

Installation in the Automatic Tank Gauge/Leak Detection System Installation Guide (p/n 000-1050) for complete probe

setup information.

Under

1.

FMS > Tanks > Tank N > Probe select Float Type

as Gas Density or Diesel Density. See Figure 2.
Enter the Density Calibration constant. This value can

2.

be obtained directly from the float that is being installed;

refer to the Density Calibration field in Figure 4.
Under

3.

FMS > Tank > Tank N > Limits, two new

parameters should appear: “High Density Limit” and

“Low Density Limit”. These limits will be set to the default

range limit, this limit can only be decreased to narrow the

expected density. The ATG will generate an alarm when

the density measurement is outside of this range. See

Figure 5.