Franklin Fueling Systems T5 Series Density Measurement Option Installation User Manual
Density measurement option, Installation guide, Overview

1
Density Measurement Option
*
Installation Guide
T5 Series
Important: The density float is very fragile. Do not to damage the float’s coating; it provides electrical character-
istics to avoid static discharge and prevent product absorption (which will cause incorrect readings).
Overview
T5 series consoles with magnetostrictive probes (TSP-LL2) serial # 6XXXXX can have the Density Measurement Option
enabled. This feature measures and reports the density of product in a tank using the same probe by adding an additional
float (called ‘density float’) that will be located around and below the product float (close to the surface of the product). The
Density Measurement Option can be useful to help a site determine the quality of the product deliveries that they receive
and whether or not they’ve been altered in any way.
Density is calculated based on the distance between the product float and the density float. Due to high accuracy require-
ments, the product float and the density float will be calibrated as a pair when they are shipped from the factory and must
not be separated in the field. If either float is damaged, both will have to be replaced at the same time. Each pair of floats will
be provided with a calibration constant that needs to be programmed into the ATG in addition to the probe gradient.
The float set will also include a water float, which does not affect density measurement and may or may not be installed.
All float sets will include one of each of the following:
•
3" product float
•
4" density float
•
4" water float
The density float part numbers are:
Part Number
Description
TSP-IGF4D
4" gasoline density float set
TSP-IDF4D
4" diesel density float set
Technical Specifications
Probe Part Number
Density Measurement Range
TSP-IGF4D
690-800 kg/m
3
TSP-IDF4D
790-900 kg/m
3
Density Measurement Accuracy
+/- 1.0 kg/m
3
Density Measurement Resolution
+/- 0.1 kg/m
3
Minimum Detectable Product Level
without water float – 170 mm (6.7")
with water float – 270 mm (10.7")
* U.S. Patent 7,278,311