Xylem Fixed speed booster sets programming manual/Electronic control board SM30 User Manual
Page 45

en
en
en
en
45
2
MIN.PRES.DELAY
Function available only with systems with a
pressure sensor and only if the respective
alarm is enabled (previous parameter).
Delay time in seconds on blocking
intervention for minimum pressure.
0..200 s
20 s
3
MAX.PRES.THRES
H.
MAX PRESSURE ALARM
Function available only with systems with a
sensor.
Maximum pressure beyond which all the
active pumps are switched off.
To disable, insert pressure = 0 bar
0..FS bar
0 bar
4
MAX.PRES.DELAY
Function available only with systems with a
sensor and if the respective alarm is
enabled (previous parameter).
Delay time in seconds on blocking
intervention for exceeding maximum
pressure.
0..10 s
0 s
5
EXT.AL. DEFINE
EXTERNAL FAULT ALARM
Configuration of the indication of an
external alarm connected to digital input
AUX2. Usually a temperature or voltage
overload alarm generated by an external
trip device.
OVERTEMPER
ATURE
OVERVOLTAGE
EXT.TRIP
DEVICE
OVER-
VOLTAGE
6
P1 OVERLOAD
P1 OVERLOAD ALARM
Intervention of thermal protection / PTC
pump 1
THERMAL PR.
PTC
DISABLED
THERMAL PR.
7
P2 OVERLOAD
P2 OVERLOAD ALARM
Intervention of thermal protection / PTC
pump 2
THERMAL PR.
PTC
DISABLED
THERMAL PR.
8
P3 OVERLOAD
P3 OVERLOAD ALARM
Intervention of thermal protection / PTC
pump 3
THERMAL PR.
PTC
DISABLED
THERMAL PR.
9
LOW WATER
ALARM
LOW WATER ALARM
Intervention of hardware protection for low
level/pressure on intake
From probe circuit HIGH. LOW, COM to
terminals 22 – 23- 24
YES
NO
YES
10
L.O.W. AL.DELAY
Delay time in seconds to block pumps for
intervention of protection for low
level/pressure on intake.
10…100 s
10 s
11
CONVEYOR LIMIT
CONVEYOR LIMIT
Tripping of protection against pump
operation below minimum pressure.
Signal arrives from minimum pressure switch
(CONV.L.SWITCH) connected to digital input
AUX3.
YES
NO
YES
12
ALARMS RESET
Resets the memory of the Alarms Log.
YES
NO
NO
Adjusting the
Adjusting the
Adjusting the
Adjusting the Minimum Pressure Switch Alarm (
Minimum Pressure Switch Alarm (
Minimum Pressure Switch Alarm (
Minimum Pressure Switch Alarm (CONV.L.SWITCH
CONV.L.SWITCH
CONV.L.SWITCH
CONV.L.SWITCH))))
The minimum pressure switch is positioned on the delivery manifold and must be set at the system
minimum pressure, about 0.5 bar below the starting pressure value of the last pump.