Xylem Fixed speed booster sets programming manual/Electronic control board SM30 User Manual
Page 44

en
en
en
en
44
Phase
Display
Comment
Field
Default
0
0
0
0 ALARM RELAY
ALARM RELAY
ALARM RELAY
ALARM RELAY
1
DELAY ON RELAY
Delay in seconds of alarm relay
activation
0..60 s
0 s
2
DELAY OFF RELAY
Delay in seconds of alarm relay
deactivation
0..60 s
0 s
3
LOGIC RELAY
Active: for event =ON
The contact is open in case of event
Passive: for event =OFF
The contact is closed in case of event
ACTIVE
PASSIVE
PASSIVE
4
DISABLE RELAY
Automatic when the alarm ceases or
manually with button P3 (EXIT)
AUTOMATIC
MANUAL
AUTOMATIC
5
RELAY ON O.L.
PUMP OVERLOAD ALARM
Activates alarm relay for tripping of an
overload/ptc of any active pump.
YES
NO
YES
6
RELAY ON L.O.W.
LOW WATER ALARM
Activates alarm relay for low
level/pressure on intake through
probes/float/min. pressure switch
YES
NO
YES
7
RELAY ON SENSOR
SENSOR ALARM
Activates relay for fault in activated
sensors.
YES
NO
YES
8
RELAY ON C.LIMIT
CONVEYOR LIMIT
Activates relay for Minimum Pressure
Switch alarm (connected to digital
input AUX3, to be set as
CONV.L.SWITCH)
YES
NO
NO
9
RELAY ON EXT.AL.
EXTERNAL FAULT ALARM
Activates relay for external fault arriving
from digital input AUX2.
YES
NO
NO
10
RELAY ON MAX P.
MAX PRESSURE ALARM
Activates relay for maximum pressure
alarm arriving from digital input AUX1
or from MAX.PRES.THRESH.
YES
NO
NO
11
RELAY ON MIN P.
MINIMUM THRESHOLD ALARM
Activates relay for minimum pressure
threshold alarm.
YES
NO
NO
6.2.8 PROGRAMMING THE ALARMS
6.2.8 PROGRAMMING THE ALARMS
6.2.8 PROGRAMMING THE ALARMS
6.2.8 PROGRAMMING THE ALARMS
Phase
Display
Comment
Field
Default
0
0
0
0 ALARMS
ALARMS
ALARMS
ALARMS
1
MIN.PRES.THRES
H.
MINIMUM PRESSURE ALARM
Function available only with systems with a
pressure sensor.
Set the minimum pressure value below
which the system interrupts pump
operation.
The system control is performed only if at
least one pump is active.
To disable, insert pressure = 0 bar
0..FS bar
0 bar