2 metering, Metering – GE Industrial Solutions IEMi User Manual
Page 8

3.1.2 Metering
The METERING mode is entered any time the “METER” button is pressed.
The LCD screen will indicate a series of screenshots showing the measures of all electric parameters like
AC, DC and various statistics.
In this mode the buttons perform the following functions:
Return to HOME screen.
Scrolls backward to the previous screen.
Scrolls forward to the next screen.
It is possible to view any pushbutton functional description by pushing the button for more than 3
seconds.
`
Home\Meter
Load on phases screen 1
… V
Output voltage PHASE/NEUTRAL for each phase.
… A
The output current as RMS values (for RPA: total
value of Parallel System).
… %
The output load as percentage (for RPA: with
respect to the rated power of Parallel System).
The source of the power supplied to the load:
- Detour ON (Q2 close) - Load on inverter
- Q1 open
SYSTEM LOAD
L1 :
277 V
180.0 A
50 %
L2 :
277 V
144.0 A
40 %
L3 :
277 V
108.0 A
30 %
LOAD ON INVERTER
- Load on bypass
- Load Off
- On battery
- Inverter OFF (IEMi)
`
Home\Meter
Load on phases screen 2
… kW
The load active power (kW) (for RPA: total value of
Parallel System).
… kVA The load apparent power (kVA) (for RPA: total
value of Parallel System).
… PF
The load power factor:
+ for inductive loads (lagging power factor).
- for capacitive loads (leading power factor).
The source of the power supplied to the load:
- Detour ON (Q2 close) - Load on inverter
- Q1 open
SYSTEM LOAD
L1 : 44.8 kW
49.8 kVA
PF +/-0.90
L2 : 35.8 kW
39.8 kVA
PF +/-0.90
L3 : 26.9 kW
29.9 kVA
PF +/-0.90
INVERTER OFF (IEMi)
- Load on bypass
- Load Off
- On battery
- Inverter OFF (IEMi)
Modifications reserved
Page 8/24
OPM_OPT_IEM_iXX_XXX_XGB_V010.doc
User Manual IEMi - Intelligent Energy Management integrated