6.2 CUSTOMER INTERFACE IM0171
X1 terminals – Output signals on voltage free contacts
X1 / 1, 2, 3
NO, C, NC
Mains Failure
(def. Parameter RL=1)
X1 / 4, 5, 6
NO, C, NC
Load on Inverter
(def. Parameter RL=3)
X1 / 7, 8, 9
NO, C, NC
Stop Operation
(def. Parameter RL=5)
X1 / 12, 13, 14
NO, C, NC
Load on Mains
(def. Parameter RL=2)
X1 / 15, 16, 17
NO, C, NC
General Alarm
(def. Parameter RL=4)
X1 / 18, 19, 20
(def. Parameter RL=6)
NO, C, NC
Acoustic Alarm
The programmable signals on X1 will be disabled with Q1 open,
with the exception of the signals for “16 - Manual Bypass ON”
and “26 - EPO”.
Input contacts
X1 / 10, 21
NO Programmable
12
8
19
21
22
20
10
11
9
17
18
16
15
7
6
5
4
12
14
13
3
2
1
X1
X2
J1
SGSE
_600_
S1_
Cus
to
m
er
int
erfa
ce_0
1
X1 / 11, 22
NO
Programmable / Generator ON
Fig. 7.2-1 Customer Interface IM0171
On terminals X1 connector, the output signals can be associated to a specific function.
This selection can be performed from the display by QUALIFIED AND TRAINED PERSONNEL (password
required).
With reference to IEMi Operation Mode, the following function is available:
27- eBoost/IEMi mode.
This signal indicates when IEMi Operation Mode is enabled and active.
Some UPS functions can be activated when an external Normally Open contact is closed on:
X1-10, 21 or X1-11, 22
The specific function can be selected from the display by QUALIFIED AND TRAINED PERSONNEL
(password required).
With reference to IEMi Operation Mode, the following function is available:
8 – eBoost/IEMi control.
When active, this function will deactivate IEMi Operation Mode.
6.3 3-PH SNMP/WEB ADAPTER
IEMi Operation Mode can be enabled, disabled and programmed via the web interface of a 3-ph
SNMP/Web adapter when this option is available in the Parallel System.
The configuration selection mirrors the parameters described in this manual.