2 alarms, Alarms – GE Industrial Solutions IEMi User Manual
Page 19

3.2.2 Alarms
The alarms mode is entered any time the
alarms button is pressed.
The LCD will display a series of screens
corresponding to the last 256 events, one event
per screen.
The buttons perform the following functions:
metering Abandons
alarms mode and enters metering mode.
alarms Next
screen.
parameters Abandons
the
alarms mode and enters the parameters mode.
+
Scrolls forward to the next screen.
–
Scrolls backward to the previous screen.
ok
Display the main screen for this mode.
01.01.2006 12:45:07
NR=255 Status=4A61
4115: LOW
BATTERY VOLTAGE
metering
alarms
parameters
+
–
ok
The information displayed includes:
•
The exact date and time when the event occurred.
•
The number of the event, 255 being the most
recent event, and 0 the oldest.
•
The standard GE code for the event and the
machine status word.
An explicit text description of the event.
Events (alarms and messages)
Alarms and Messages are differently specified because the alarms are indicating an abnormal
functioning of the UPS (which are additionally signaled with the LED Alarm and acoustically with the
buzzer), while the messages indicate the various states of operation of the UPS (stored in the events list,
but not activating the LED alarm and the acoustical alarm).
Code
Alarms
Meaning
4608
The propagation of the IEMi Operation Mode configuration
to other units in a Parallel System failed.
ECO CONFIG FAILURE
Code
Message
Meaning
4604
COMMAND IEMi ON
The IEMi Operation Mode function is enabled, and
according to the time program the UPS system will run in
IEMi Operation Mode.
4605
COMMAND IEMi OFF
The IEMi Operation Mode has been disabled or the
programmed time is expired.
The UPS returns to VFI Operation Mode supplying the Load
normally by Inverter.
4606
IEMi ACTIVATION ALLOWED
IEMi control signal has been cleared on the Customer
Interface Board (X1 - 11, 22).
IEMi Operation Mode depends on scheduled activation of
the functions.
4607
IEMi ACTIVATION INHIBITED
Customer Interface Board (X1 - 11, 22) received an IEMi
control signal.
IEMi Operation Mode will be temporarily inhibited.
Modifications reserved