9 rpa parallel system connection, 1 power wiring of parallel units, Rpa parallel system connection – GE Industrial Solutions SG Series 50 & 80 kVA Installation Guide User Manual
Page 29: Power wiring of parallel units
3.9 RPA PARALLEL SYSTEM CONNECTION
WARNING !
This operation must be performed by trained personnel before the initial start-up.
ENSURE THAT THE UPS INSTALLATION IS COMPLETELY POWERED DOWN.
3.9.1 Power wiring of parallel units
To guarantee good Load sharing between the units of a parallel system, we recommend that the cable
length from the input distribution board (5) to the output distribution board (10) is equal for each unit
(a+b = c+d = e+f = g+h = i+l = m+n = o+p = q+r).
Tolerance: +/-10%.
The AC input power of the Bypass must be the same for all units of the parallel system - no phase shift
allowed between units.
NOTE !
It is strongly recommended that no transformers, automatic circuit breakers or fuses
should be inserted between the unit’s output and the Load common bus bars.
However, it is recommended that a disconnection or isolation switch is installed in
order to totally isolate a unit if needed.
Fig. 3.9.1-1 RPA Parallel System
1 = Rectifier
c
=
UPS Number 1
2 = Inverter
2
=
UPS Number 2
3 = Electronic
Bypass
3
=
UPS Number 3
4 = Manual
Bypass
4
=
UPS Number 4
5 = Input
Utility
Distribution
5
=
UPS Number 5
6 = Unit Output Load
6
=
UPS Number 6
7 = External
Battery
MCB
7
=
UPS Number 7
8 = External
Battery
fuse
8
=
UPS Number 8
9 = External
Battery
10 = Common Busbar and Output Load Distribution
Modifications reserved
Page 29/38
OPM_SGS_ISG_50K_80K_0US_V040.doc
Installation Guide SG Series 50 & 80 kVA