Installation guide, Configuration, Default dip switch settings – GE Industrial Solutions ASPMETER Install User Manual
Page 5

TM
ASPMETER
INSTALLATION GUIDE
Z206024-0B
PAGE 5
©2011 For technical support please contact
10111
DET-756
our GE tech support team at 1-800-GE-1-STOP (1-800-431-7867)
CONFIGURATION
1. Communications Configuration: Communications parameters for the ASPMETER
series are field selectable for your convenience. Please see the Product Diagram
section (page 2) for selector location. The following parameters are configurable:
• Baud Rate: 9600, 19200, 38400
• Parity On or Off
• Parity: odd or even
• Wiring: two or four
B
ø
Reserved
B1 Off/
On
Parity
2/4
Wire
Odd/
Even
Parity
Example: 2-wire 19200 Baud No Parity (Default Only)
1
2
3
4
5
6
7
8
off
off
X
X
X
9600
on
off
X
X
X
19200
off
on
X
X
X
38400
on
on
X
X
X
Reserved
off
off
X
X
X
No Parity
on
off
X
X
X
Odd Parity
off
on
X
X
X
No Parity
on
on
X
X
X
Even Parity
on
X
X
X
4-wire RS-
485
off
X
X
X
2-wire RS-
485
2. Address Configuration: Each Modbus device on a single network must have a
unique address. Set the switch block to assign a unique address before the device
is connected to the Modbus RS-485 network. If an address is selected which
conflicts with another device, neither device will be able to communicate.
3. Address the ASPMETER as any whole number between and including 1-246. Each
unit is equipped with a set of 8 DIP switches for addressing. See below.
1
LSB
MSB
1 2 4 8 16 32 64 128
DIP Switch Values
=
4. To determine an address, simply add the values of any switch that is on.
For example:
40
=
LSB
MSB
Switch number 4 has an ON Value of 8 and switch number 6 has an ON Value of 32.
(8 + 32 = 40). Therefore, the address for the ASPMETER is 40.
See the Address Setup section (page 8) for a pictorial listing of the first 63 switch
positions.
DEFAULT DIP SWITCH SETTINGS
The ASPMETER includes two DIP switches, as shown below. Switches are shown in
their default positions.
Comms Address
Comms Settings