Smr2 modbus user manual – GE Industrial Solutions Record Plus FG600 SMR2 Modbus User Manual
Page 17

SMR2 Modbus User Manual
Reg Contents Units/
Range
Type
R/W
Format
2000
Event Code – Event 1
0-256
RO
Unsigned int
2001 Hour
0
RO Unsigned
int
2002 Minute
0
RO Unsigned
int
2003 Second
0
RO Unsigned
int
2004 Milliseconds
0
RO Unsigned
int
2005
Event specific data 1
0 - 65535
RO
Unsigned int
2006
Event specific data 2
0 - 65535
RO
Unsigned int
2007
Event specific data 3
0 - 65535
RO
Unsigned int
2008
Event code – Event 2
0-256
RO
Unsigned int
2009 Hour
0
RO Unsigned
int
2010 Minute
0
RO Unsigned
int
2011 Second
0
RO Unsigned
int
14
If another event occurs before the master reads all the
existing events, the oldest event is lost, new event data
will be placed in the EVENT 8 register, and the older
event register contents are shifted. The total number of
events since the last reset will be kept counted at
register location 1000-1001. Events are read using
Function Code 04.
2012 Milliseconds
0
RO Unsigned
int
2013
Event specific data 1
0 - 65535
RO
Unsigned int
2014
Event specific data 2
0 - 65535
RO
Unsigned int
2015
Event specific data 3
0 - 65535
RO
Unsigned int
… …
…
… …
2056
Event code – Event 8
0-256
RO
Unsigned int
2057 Hour
0
RO Unsigned
int
2058 Minute
0
RO Unsigned
int
2059 Second
0
RO Unsigned
int
2060 Milliseconds
0
RO Unsigned
int
2061
Event specific data 1
0 - 65535
RO
Unsigned int
2062
Event specific data 2
0 - 65535
RO
Unsigned int
2063
Event specific data 3
0 - 65535
RO