MicroVersaTrip Plus™ and MicroVersaTrip PM™ Trip Units

Chapter 1. Introduction

4

C

C

C

Ch

h

h

haa

a

arrrraa

a

accc

ctttteee

errrr

M

M

M

Maa

a

ax

x

x

xiiiim

m

m

mu

u

u

um

m

m

m A

A

A

Allllllllo

o

o

ow

w

w

waa

a

ab

b

b

blllleee

e

C

C

C

CT

T

T

T

2

2000 A

3

2500/3000/3200 A

4

4000 A

5

5000 A

Table 2. Breaker frame size maximum CT referred to by second

character of Trip Unit catalog number.

The third and fourth characters of the catalog
number indicate the CT that is actually installed in
the breaker, as listed in Table 3. The table also indi-
cates whether each CT is available with only RMS9C
Trip Units or with both types.

C

C

C

Ch

h

h

haa

a

arrrraa

a

accc

ctttteee

errrrssss

C

C

C

CT

T

T

T SSS

Siiiizzzzeee

e

T

T

T

Trrrriiiip

p

p

p U

U

U

Un

n

n

niiiitttt SSS

Seee

errrriiiieee

essss

01

150 A

RMS9C

02

200 A

both

03

225 A

RMS9C

04

400 A

both

06

600 A

RMS9C

08

800 A

both

10

1000 A

both

16

1600 A

both

20

2000 A

both

25

2500 A

both

30

3000 A

both

32

3200 A

RMS9C

40

4000 A

both

50

5000 A

RMS9C

Table 3. Installed breaker CT size referred to by third and

fourth characters of Trip Unit catalog number.

The fifth character of the catalog number is the let-
ter L, which indicates that all Trip Units come with
long-time overcurrent protection. Additional letters
are appended to the catalog number to indicate
installed protective functions, as in Table 4. These
suffixes are valid for both MicroVersaTrip Plus and
MicroVersaTrip PM style Trip Units. They are
appended from left to right in the order given.

SS

S

Su

u

u

uffffffffiiiix

x

x

x

P

P

P

Prrrro

o

o

otttteee

eccc

cttttiiiivvvveee

e F

F

F

Fu

u

u

un

n

n

nccc

cttttiiiio

o

o

on

n

n

n

S

Short-time overcurrent protection

I

Instantaneous overcurrent protection

H

Fixed high-range instantaneous

K

Fixed high-range instantaneous (AKR-30S
only)

G

Ground fault

GD

Defeatable ground fault (not UL listed)

Z1 or

Z2

Zone-selective interlock:

Z1 – ground fault only
Z2 -– ground fault and short time

X

Switchable instantaneous/short time and

ground fault (AKR only, not UL listed)

Table 4. Trip Unit catalog number suffixes for optional

functions.

MicroVersaTrip PM catalog numbers contain an
additional one- or two-letter suffix to indicate the
communication, metering, and relaying functions
installed, as shown in Table 5. MicroVersaTrip Plus
catalog numbers do not have this final suffix.

SS

S

Su

u

u

uffffffffiiiix

x

x

x

F

F

F

Fu

u

u

un

n

n

nccc

cttttiiiio

o

o

on

n

n

n

(none)

MicroVersaTrip Plus Trip Unit

PM

Metering, relaying, and communication

M

Metering and communication

P

Relaying and communication

Table 5. MicroVersaTrip PM Trip Unit suffixes for

communication, metering, and relaying.

Finally, if the Trip Unit is ordered as a replacement,
an “R” suffix is appended to the catalog number.

For example, a Trip Unit with catalog number
B210LSIGZ1PM has the following functions:

B2 -- Trip Unit for Power Break II with maximum

CT of 2000 A

10 – breaker current sensor (CT) of 1000 A

L -- long-time overcurrent protection

S -- short-time overcurrent protection
I -- adjustable instantaneous protection

G -- ground-fault protection

Z1 – ground-fault zone-selective interlock