Absolute maximum ratings, Electrical specifications, Data sheet – GE Industrial Solutions Austin MicroLynx II 12V SIP User Manual
Page 2: Austin microlynx
![background image](/manuals/295225/2/background.png)
Data Sheet
January 18, 2010
Austin MicroLynx
II
TM
12V SIP Non-isolated Power Modules:
8.3 – 14Vdc input; 0.75Vdc to 5.5Vdc Output; 6A output current
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are
absolute stress ratings only, functional operation of the device is not implied at these or any other conditions in
excess of those given in the operations sections of the data sheet. Exposure to absolute maximum ratings for
extended periods can adversely affect the device reliability.
Parameter
Device
Symbol
Min
Max
Unit
Input Voltage
All
V
IN
-0.3 15 Vdc
Continuous
Sequencing voltage
All
Vseq
-0.3
V
IN,max
Vdc
Operating Ambient Temperature
All
T
A
-40 85 °C
(see Thermal Considerations section)
Storage Temperature
All
T
stg
-55 125 °C
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, resistive load, and temperature
conditions.
Parameter
Device
Symbol
Min
Typ
Max
Unit
Operating Input Voltage
V
o,set
≤ 3.63
V
IN
8.3 12 14 Vdc
V
o,set
> 3.63
V
IN
8.3 12 13.2
Vdc
Maximum Input Current
All
I
IN,max
4.5
Adc
(V
IN
= V
IN, min
to V
IN, max
, I
O
=I
O, max
)
Input No Load Current
V
O,set
= 0.75 Vdc
I
IN,No load
17
mA
(V
IN
= V
IN, nom
, Io = 0, module enabled)
V
O,set
= 5.5 Vdc
I
IN,No load
100
mA
Input Stand-by Current
All
I
IN,stand-by
1.2
mA
(V
IN
= V
IN, nom
, module disabled)
Inrush Transient
All
I
2
t
0.4 A
2
s
Input Reflected Ripple Current, peak-to-peak
(5Hz to 20MHz, 1μH source impedance; V
IN, min
to
V
IN, max,
I
O
= I
Omax
; See Test configuration section)
All
30
mAp-p
Input Ripple Rejection (120Hz)
All
30
dB
CAUTION: This power module is not internally fused. An input line fuse must always be used.
This power module can be used in a wide variety of applications, ranging from simple standalone operation to being
part of a complex power architecture. To preserve maximum flexibility, internal fusing is not included, however, to
achieve maximum safety and system protection, always use an input line fuse. The safety agencies require a fast-
acting fuse with a maximum rating of 6 A (see Safety Considerations section). Based on the information provided in
this data sheet on inrush energy and maximum dc input current, the same type of fuse with a lower rating can be
used. Refer to the fuse manufacturer’s data sheet for further information.