GE Industrial Solutions Spectra II Series Plug-in and Feeder Busway with BlueCoat Epoxy Insulation System User Manual
Page 26

Spectra and Spectra II Series™ Plug-In and Feeder Busway 
Installing Spectra II Series Busway 
 
24
3. Align sections to be joined by matching up
―Ø side‖ labels attached at ends of each 
section. 
4. If necessary, loosen joint bolt slightly. 
5. Slide sections together. Make sure that the 
busbars interweave the insulators as shown 
in Figure 36-38. NOTE: the housing ground 
side plates must pass between the outside 
insulators and the joint sides. 
6. The standard distance between the
housings is 9‖ as shown in Figure 37. 
However, the joint is also adjustable as 
shown in Figures 36-38. Simply move the 
sections in or out to the desired length as 
shown and remove the twist outs in both 
joint caps. See Figure 39 NOTE: Remove 
shipping screw to center joint when 
adjusting to max. and min. length. 
7. Insert mounting screws into the joint cap
which is already attached and tighten to 
align centerlines of the two bus sections. 
8. Inspect busway run for the straightness in
all planes, and make adjustments, if 
necessary, for good alignment. 
9. Lubrication grease has been applied to the
joint bolt head and thread to reduce friction. 
Do not remove this grease. 
10. Tighten the joint bolt to 50 foot-pounds.
When the Belleville springs on both sides are 
flattened, the bolt is fully torqued. The bolt 
head may be relocated to the opposite side 
of the busway if it is inaccessible. 
11. Install second joint cap and tighten the joint
cap screws.
12. During installation occasional meggering
should reveal any improperly made 
assemblies. Resistance should not drop 
below one megohm for 100 feet of busway. 
Megger the complete run before energizing. 
 
To Remove the Joint or Captive Piece of 
Busway 
Should it become necessary to isolate for 
testing or troubleshooting a piece or run off 
Spectra and Spectra II Series ™ busway the 
joint is designed for easy removal either during 
or after installation. 
1. De-energize the busway. Remove either 
joint cap.
2. Remove the shipping screw, illustrated in
Figure 37.
3. Grasp the joint sides and pull toward the
narrow side of the busway. A gently rocking 
motion may necessary to aid the joint in 
sliding out. 
NOTE: With the joint removed the busway is 
segmented and section of the run away 
from the source is electrically isolated from 
the source. 
4. To reinstall the joint, simply slide the joint
back into place. CARE MUST BE TAKEN TO 
ASSURE SPLICE PLATES AND INSULATORS 
ARE PROPERLY POSITIONED. It is not 
necessary to reinstall the shipping screw. 
5. Install joint cap(s), as required. 
6. Megger at 1000VDC the complete run of 
busway before energizing.
Joints With +/- .50 Inch Adjustability
Figure 36 “Minimum”
Figure 37 “Standard”
