Data sheet, Electrical specifications (continued), Isolation specifications – GE Industrial Solutions EVK011A0B Series (Eighth-Brick) User Manual
Page 3: General specifications
GE
Data Sheet
EVK011A0B Series (Eighth-Brick) DC-DC Converter Power Modules
36–60Vdc Input; 12.0Vdc Output; 11A Output Current
May 15, 2013
©2012 General Electric Company. All rights reserved.
Page 3
Electrical Specifications (continued)
Parameter
Device
Symbol
Min
Typ
Max
Unit
Nominal Output Voltage Set-point
All V
O, set
11.76 12.0 12.24 V
dc
V
IN
=V
IN, min
, I
O
=I
O, max
, T
A
=25°C)
Output Voltage
All
V
O
-3.0
+3.0 %
V
O, set
(Over all operating input voltage, resistive load, and
temperature conditions until end of life)
Output
Regulation
Line (V
IN
=V
IN, min
to V
IN, max
) All
0.2 %
V
O, set
Load (I
O
=I
O, min
to I
O, max
)
All
0.2 %
V
O, set
Temperature (T
ref
=T
A, min
to T
A, max
) All
1.0 %
V
O, set
Output Ripple and Noise on nominal output
(V
IN
=V
IN, nom
,I
O
= I
O, max
, T
A
=T
A, min
to T
A, max
)
RMS (5Hz to 20MHz bandwidth)
All
30 mV
rms
Peak-to-Peak (5Hz to 20MHz bandwidth)
All
100 mV
pk-pk
External Capacitance
All
C
O
100
2,000
μF
Output Current
All
I
o
0
11 A
dc
Output Current Limit Inception (Hiccup Mode )
All
I
O, lim
105 115 130 % I
o
(V
O
= 90% of V
O, set
)
Output Short-Circuit Current
All I
O, s/c
3 5 A
rms
(V
O
≤250mV) ( Hiccup Mode )
Efficiency All
η 95 %
V
IN
= V
IN, nom
, T
A
=25°C
I
O
=I
O, max ,
V
O
= V
O,set
Switching Frequency (Input ripple is ½ f
sw
) All
f
sw
330 kHz
Dynamic
Load
Response
(dIo/dt=0.1A/s; V
IN
= V
IN, nom
; T
A
=25°C)
Load Change from Io= 50% to 75% or 25% to 50%
of Io,max;
Peak Deviation
All
V
pk
3
% V
O, set
Settling Time (Vo<10% peak deviation)
All t
s
200
s
(dIo/dt=1A/s; V
IN
= V
IN, nom
; T
A
=25°C)
Load Change from Io= 50% to 75% or 25% to 50%
of Io,max;
Peak Deviation
All
V
pk
5
% V
O, set
Settling Time (Vo<10% peak deviation)
All t
s
200
s
Isolation Specifications
Parameter
Device
Symbol
Min
Typ
Max
Unit
Isolation Capacitance
All
C
iso
1000
pF
Isolation Resistance
All
R
iso
10
MΩ
I/O Isolation Voltage (100% factory Hi-pot tested)
All
All
2250 V
dc
General Specifications
Parameter
Device
Symbol
Min
Typ
Max
Unit
Calculated Reliability based upon Telcordia SR-332
Issue 2: Method
I
Case 3 (I
O
=80%I
O, max
, T
A
=40°C,
airflow = 200 lfm, 90% confidence)
All FIT
315.1
10
9
/Hours
All MTBF
3,173,243
Hours
Weight (Open Frame)
All
19
(0.67)
g
(oz.)