GE Industrial Solutions CPS3200U User Manual
Cps3200u technical support guide
Table of contents
Document Outline
- Hardware
- Brief Hardware Orientation
- Always look first at the alarm card to establish valid A and B power feeds to both sides of the shelf.
- Once both the “A” and the “B” input power LEDs are green, other LEDs can be used to diagnose other faults.
- The Shelf ID rotary DIP switches are as shown here:
- Converter LEDs look like this:
- Alarm Reference Table
- Locating Failed Fans
- 2 WEB
- The web page reflects the physical configuration of each shelf.
- To help find the FTTN relevant information on each tab, please use this guide
- To interact with the QS941 Controller through the WEB interface it is possible to connect a computer to the QS941A directly using server mode or through a LAN using client mode.
- 3 Front Panel