SPECIFICATIONS
Rev. Sept. 2012
ES
015-10
ES
030-5
ES
075-2
ES
0300-0.45
Out put
volt age
cur rent
0 - 15 V
0 - 10 A
0 - 30 V
0 - 5 A
0 - 75 V
0 - 2 A
0 - 300 V
0 - 450 mA
In put
AC sin gle phase, 48 - 62 Hz
rated volt age range
rated fre quency
In put cur rent @ 230 VAC
power fac tor, 110 / 230 VAC
full load
DC
in ter nal fuses
standby in put power (Vo=Io=0)
standby in put power (Vo=Vmax)
90 - 265
V
100 - 240 V
50 / 60 Hz
1 A
0.99 / 0.83
con tact fac tory
4 AT
6 W
11 W
Ef fi ciency
AC 230 V in put, full load
AC 110 V in put, full load
83 %
80 %
84 %
82 %
84 %
81 %
84 %
81 %
Reg u la tion
Load 0 - 100%
CV
in ter nal sens ing
op tional ex ter nal sens ing
Line 90 - 265 V AC
CV
15 mV
2 mV
0.2 mV
6 mV
2 mV
0.5 mV
5 mV
5 mV
1 mV
10 mV
10 mV
3 mV
Load 0 - 100%
CC
Line 90 - 265 V AC
CC
(in ter nal volt age sens ing)
3 mA
0.5 mA
1 mA
0.2 mA
0.5 mA
0.1 mA
0.3 mA
0.05 mA
Rip ple + noise (full load)
rms
(BW=300 kHz)
CV
p-p
(BW=20 MHz)
CV
rms
(BW=300 kHz)
CC
p-p
(BW=20 MHz)
CC
0.5 mV
8 mV
1.5 mA
10 mA
0.6 mV
10 mV
0.5 mA
2 mA
1 mV
15 mV
0.1 mA
0.5 mA
7 mV
50 mV
(typ i cal 30 mV)
0.03 mA
0.2 mA
Temp. coeff., per °C
CV
CC
5.10
-5
10.10
-5
Sta bil ity af ter 1 hr warm-up
dur ing 8 hrs
CV
CC
tamb = 25 ± 1 °C, Vin = 230 VAC
(in ter nal volt age sens ing for CC-stab.)
10.10
-5
10.10
-5
10.10
-5
10.10
-5
10.10
-5
10.10
-5
10.10
-5
12.10
-5
An a log Pro gram ming
CV
CC
Pro gram ming in puts
in put range
ac cu racy
off set
temp. coeff. off set
in put im ped ance
0 - 5 V
± 0.2%
0 …
+
3 mV (on 5 V)
10
µV / °C
1 MOhm
0 - 5 V
± 0.8%
0 …
+
10 mV (on 5 V)
60 µV / °C
1 MOhm
Mon i tor ing out put
out put range
ac cu racy
off set
temp. coeff. off set
out put im ped ance
0 - 5 V
± 0.2%
– 1 …
+
1 mV (on 5 V)
10 µV / °C
2 Ohm / max. 4 mA
0 - 5 V
± 0.8%
– 10 … 0 mV (on 5 V)
60 µV / °C
2 Ohm / max. 4 mA
Ref er ence volt age
on prog. con nec tor
Vref
TC
5.137 ± 10 mV (Ro = 2 Ohm, max. 4 mA)
50 ppm
+12 V out put
Vo
on prog. Con nec tor
Ro
12 V ± 0.5 V
100 Ohm