(Subject to alterations. This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)

Remote Shutdown

Enable a 18…30Vdc 20mA voltage
signal to (Rmt/Rm) to shutdown the
HSD, the yellow LED lights and 0V
is distributed to the outputs.
If the shutdown is short circuited or
<500mV are applied to (Rmt/Rm),
the HSD „tickers“, the yellow LED
flashes and Uout <5V is distributed
to the outputs.
Disable the remote voltage to restart
the HSD

Power Good Control

Low Voltage:
If adjusted Vout drops 10% the red LED lights
and the DC-OK-Relay (Re) drops (control
message). The green DC-OK LED is off.
Overload: If <0.9xVout applies to the outputs,
the red LED lights and the DC-OK-Relay (Re)
drops (control message). The green DC-OK
LED is off.
Vout o.k. = relay closed
Vout fail = relay open

Series Connection

Redundant Connection

Inrush Current Limitation (Block Diagram)


To increase the output power, equal
HSD devices can be used series
connected. Observe to safety
directives when the output voltage
achieves 60Vdc in sum.


To increase system availability up to
fife HSD can be used in parallel
operation mode. Please make sure
that wiring length from all units to
the load is equal. Full redundant
operation modes require external
diodes.
We suggest to use our RED00202
DIN-Rail N+1 redundant module für
professional redundancy.

While connecting the HSD to the AC
wire network its inrush current is
limted to <20Apeak/14,4Aeffective.
The start capacitors are loaded after
20ms and the HSD actuates. After
passing softstart the power supply
is ready for operation after a total of

Ʌ

t=400ms.

Characteristics Vi=400Vac:
Peak Inrush Current = <14,4Aeff.
Peak Limiting Duration = 20ms

Power Boost and Temperature Behaviour


The HSD10001 operates in accordance to the V/C-characteristic line (see
graph I/Boost on page 2). It has a determinate power reserve (boost): With
ambient temperatures

40°C the power boost is continuously available

while with higher ambient temperatures it is available for a few minutes.
When a DC short circuit or an overload occurs to the HSD10001, it is
limited to I/Boost (see graph) but it is not shot down. The DC-voltage is
lowered until the error is rectified. The V/C-line and the power boost apply
operation of critical loads, like DC-DC-converters, capacitive loads, drives
and batteries trustworthy.

Output voltage/current ratio to ambient (U/I to °C)

Uout

40°C/Iout 60°C/Iout Uout

40°C/Iout

60°C/Iout

10Vdc

50,0A

50,0A

36Vdc

31,0A

28,0A

12Vdc

50,0A

50,0A

40Vdc

27,0A

25,0A

15Vdc

50,0A

50,0A

46Vdc

24,0A

22,0A

22Vdc

45,0A

43,0A

48Vdc

23,0A

21,0A

24Vdc

45,0A

40,0A

53Vdc

21,0A

20,0A

26Vdc

42,0A

37,0A

60Vdc

18,0A

17,0A

28Vdc

38,0A

34,0A

65Vdc

17,0A

16,0A

30Vdc

35,0A

32,0A

72Vdc

15,0A

14,0A

32Vdc

34,0A

31,0A

86Vdc

12,6A

11,7A

34Vdc

32,0A

31,0A

Test

Time A

B

C

D

Type test and factory tests are
conducted by the manufacturer.
Do not repeat the test in field.
Field test rules:

Type Test

60s

2500Vac 3000Vac 500Vdc 500Vdc

Factory Test 5s

2000Vac 2000Vac 500Vdc 500Vdc

Field Test

2s

2000Vac 2000Vac 500Vdc 500Vdc

a)

Use approriate test equipment which apply the voltage with a slow ramp

b)

Connect L1,L2 and L3 together, as well as all output poles

c)

Use only AC test-voltages with 50/60Hz. The output voltages is floating and has
no ohmic reference to ground.

d)

If testing output voltages are

60Vdc remain to security directives.

Use only isolated screw drivers to adjust output voltages.

Function Table and Messages

Indicators

DC-ok
LED green

Overload
LED red

Shutdown LED
yellow

DC-ok Relay

Normal operation

On

Off

Off

Closed

Power boost

On

Off

Off

Closed

Overload (0.9xVout)

Off

On

Off

Open

Shutdown with open contact On

Off

Off

Closed

Shutdown with 10..30Vdc

Off

Off

On

Open

Shutdown with <500mVdc

Off

Pulse

Pulse

Open

Temperature shutdown

Off

Off

Off

Open

Input voltage low or fail

Off

Off

Off

Open