Powersolve SS (DC) Series User Manual
Inverter series, Ups/inverters, Specification
www.powersolve.co.uk
Powersolve Electronics Ltd. 8A, Arnhem Road, Newbury, RG14 5RU. England
Tel:01635 521858 Fax: 01635 523771 Email: [email protected]
Specification
200 VA - 12 kVA
•
Sinusoidal Output from 12-480 V
•
Compact Switched Mode Design
•
DC Inputs 10-400 V
•
Wall or Rack Mounting
•
Industrial Grade
•
Customised Design Available
Inverter Series
Input
Input Voltage
• See Table
No load Input Power
• 20 W typical
Earth Leakage Current
• <3.5 mA at 230 VAC
Output
Output Voltage
• See Table
Output Voltage
• 110 V version 110 V to 125 V
Adjustment
230 V version 210 V to 245 V
Minimum Load
• No minimum load required
Wave Form
• Sinusoidal standard, optional wave
shape programmable
by external signal
Frequency
• Crystal stabilized 50 Hz, 60 Hz,
400 Hz or 45 to 400 Hz adjustable
Distortion
• 3% typical (5% at 400 Hz)
Rise Time
• 100 ms typical
Power Factor
• Cos Ø≥0.7 inductive/capacitive
Crest Factor
• 3
Line Regulation
• 0.1% for CI models,
2.0 % for I, IT & IV models
(±10% change Vin)
Load Regulation
• 50/60 Hz 1% typical 3% max,
400 Hz 3% typical 5% max
(10-90% load change)
Overload
• Current limited to approx 105%
Protection
I Nom (Steady State)
Short Circuit
• Electronically limited to 3 x I Nom
Current
Surge Power
• 2 x P Nom for 1 sec
Temperature
• 0.05%/°C typical
Coefficient
1
General
Efficiency
• 85-95% I models,
75-90% CI, IT & IV models
Isolation
• 3500 VDC Input to Output,
3500 VDC Input to Ground,
3500 VDC Output to Ground
Switching Frequency
• Approx 33 kHz converter & 20 kHz
Inverter section
MTBF
• 120,000 hours I & IT models,
70,000 hours CI models,
50,000 hours IV models
Dimensions/Weight
• Contact Sales
Options
• Contact Sales
Environmental
Operating Temperature • -20 °C to +75 °C, derate linearly at
2.5%/°C from +55 °C
Optional -40 °C to +75 °C
Storage Temperature
• -40 °C to +85 °C
Cooling
• Natural convection
(IT5600 to IT5800 forced cooled)
Operating Humidity
• 5-95% RH non-condensing
Operating Altitude
• 1000 m
EMC & Safety
Emissions
• EN55022 Level A conducted,
optional Class B
EFT/Burst
• EN61000-4-4 Level 3
Surge
• EN61000-4-5 Level 3
Safety Approvals
• EN60950