1 voltage at low frequencies (u/f- curve), 1 starting values, Ui r – R&M Materials Handling VARIABLE SPEED CONTROLS ControlMaster Select Service Manual User Manual
Page 19: 2 midpoint voltage adjustment, 3 zero frequency voltage adjustment, 4 test run, And i

R&M Materials Handling, Inc.
4501 Gateway Boulevard
Springfield, Ohio 45502
P.: (937) 328-5100
FAX: (937) 325-5319
19/46
R&M Materials Handling, Inc. reserves the right to alter or amend the above information without notice.
5.4.1 Voltage at low frequencies (U/f- curve)
Following parameters need to be set for U/f setting. For listed motors, values of these parameters are
stored into the inverter memory, but they can also be set manually or by Autotuning. The manual setting
procedure is as follows:
5.4.1.1 Starting values
Value
U
N
P1.2.1
Motor nominal voltage
From motor nameplate
V
f
N
P1.2.4.1
Motor nominal frequency
From motor nameplate
Hz
I
N
P1.2.4.2
Motor nominal current
From motor nameplate
A
R
S
Not
parameter
Stator resistance of motors + cable
resistance
Resistance between phases. Measured on
disconnected motor cable ends at terminal X1.
Ohm
I
0
P1.2.4.3
Flux current
From motor nameplate
(if not available, set to value 0,5*I
N
)
A
U
f0
P1.2.5.1
Zero frequency voltage % of nominal
voltage (voltage at 0Hz)
N
S
U
I
R
0
*
*
100
%
U
mid
P1.2.5.2
Midpoint voltage % of nominal voltage
(voltage at f
mid
)
0
*
41
,
1
f
U
%
f
mid
P1.2.5.3
Midpoint
frequency
100
*
0
N
f
f
U
Hz
#
If several motors are connected in parallel, the correct value of R
S
is the resistance of one motor
divided by the number of motors. The correct value of I
N
and I
0
are the value of one motor multiplied
by the number of motors
5.4.1.2 Midpoint voltage adjustment
-
Check that there is no load on the crane.
-
Set minimum speed for both directions (P1.1.4) to value f
mid
.
-
Drive at maximum speed and check the motor current from parameter V2.5.
-
Drive at minimum speed. Motor current should be approximately average of measured maximum speed current
and the I
N
.
-
Adjust value of parameter U
mid
(P1.2.5.2) until current at minimum speed (= f
mid
) is within desired range.
5.4.1.3 Zero frequency voltage adjustment
-
Set minimum speed for both directions (P1.1.4) to value 0.5 * f
mid
.
-
Drive at minimum speed. Motor current should be approximately average of measured maximum speed current
and the I
N
.
-
Adjust value of parameter U
f0
(P1.2.5.1) till current at minimum speed (=0.5 * f
mid
)
is within desired range
5.4.1.4 Test run
-
Set minimum speed for both directions (P1.1.4) to desired minimum speed.
-
Drive at minimum speed with nominal load to both directions.
-
If motor is not driving at minimum speed, increase values of parameters U
f0
and U
mid
, then continue from
Midpoint voltage adjustment.
#
If the main girder is new, it might be necessary to drive trolley several times with no load from end
to end, before beginning of u/f-curve tuning.