3 INSTALLATION
3.1 Cubicles
Wall mounting
Standard cubicle
Cubicle size (mm)
DMHR01F90, External
Braking resistor unit (mm)
002F
-
400 x 400
325 x 170 x 147 (optional)
003F – 004F
EEC25.4025
400 x 400
325 x 170 x 147
Through panel mounting
Standard cubicle
Cubicle size (mm)
D2RP03F21R2S0-6, External Braking
resistor unit (mm)
003F – 004F
EEO25.604
400 x 600
-
005F – 011F
½ CC600E
600 x 1000
-
015F
½ KA220D2
1000 x 1000
-
018F – 022F
KA220D2
1000 x 1000
Included
EEO25.604
250
400
003 - 005
Trough panel
mounted
1000
300
CC600E
630
005 - 011
600
KA220D2
338
1000
015
1000
EEC25.4025
400
250
002 - 004
wall mounted
400
Free
Free
KA220D2
338
1000
018 - 022
1000
D2RP...
3.2 Power
cabling
3.2.1 Shielded motor cable
In crane application inverter fulfills EN61800-3/A11 - second environment radiated emission requirements
without shielded motor cable.
In the second environment, shielded motor cable is recommended to use in fixed installations, especially
in buildings. However motor cables in crane and festoon power supplies are normally not shielded due to
the practical reasons.
3.2.2 Double collectors
If the power is supplied to the crane via conductor rails, double collectors are needed. This ensures a
reliable contact with the rail in all circumstances. Short interruptions and sparks between the conductor
rail and the collector may cause nuisance tripping or other undesired operations and in worst case even
permanent damage to components.
3.2.3 Cable selection
Cabling for inverter can be done using normal crane cables. All the cables must be dimensioned
according to local regulations. Ambient temperature, cabling method (size of bunches etc.) and allowable
current for the cable in use must be taken into consideration. If there are no other regulations, following
values can be used (three phase 400V supply).