Duro-Last EPS Fiberglass Facer User Manual

Page 2

background image

Duro-Last, “World’s Best Roof” and Duro-Guard are registered marks owned by Duro-Last, Inc.

Updated: 11/4/2013

2 of 2

www.duro-last.com

800-248-0280

DURO-GUARD

®

EPS FIBERGLASS FACER

Installation:

Duro-Guard EPS Fiberglass Facer may be

used directly under the Duro-Last
membrane. Care should be taken to ensure
that “bare” EPS is never in direct contact
with the membrane. Refer to the appropriate
Duro-Last specification for slip sheet and
cover board requirements.

• Panels must be kept dry before, during and

after installation. Install only as much insulation
as can be covered the same day with
completed roofing.

• The use of multiple layers of insulation with

joints staggered between layers a minimum of
6 inches is recommended to eliminate thermal
bridging.

• Butt panel edges together and stagger joints of

adjacent panels.

• Boards must be neatly fitted to roof deck and

around penetrations with no gaps greater than
¼ inch.

• Refer to the appropriate Duro-Last roof system

specification and detail drawings for deck
preparation and attachment requirements.

• Precautions must be taken to ensure that new

concrete decks have fully hydrated and do not
continue to release moisture.

Panel Attachment:

Mechanical Attachment

• When installing multiple layers (which may

include insulation, cover boards and thermal
barriers) it is acceptable to mechanically secure
through all layers.

• Use fasteners and plates supplied by or

approved by Duro-Last, Inc.

Storage:

• Insulation must be protected from open flame

and kept dry at all times.

• Factory applied packaging is intended only for

protection during transit. Slit or remove the
packaging to prevent accumulation of
condensation.

• Store elevated (at least 3”) and completely

covered with a weatherproof covering such as
a tarpaulin.

• Do not use panels which are wet or damaged.

Limitations:

• Duro-Last, Inc. will not be responsible or liable for

any defects or problems related to building or roof
design by others, to deficiencies in construction,
to dangerous conditions on the job site, or to

improper storage, handling or installation by
others.

TABLE 2. TYPICAL THERMAL VALUES

THICKNESS* R-Value

inches

mm TYPE

VIII

1.00 25

4.2

1.50 38

6.3

2.00 51

8.4

2.50 64

10.5

3.00 76

12.6

3.50 89

14.7

4.00 102

16.8

4.50 114

18.9

5.00 127

21

5.50 140

23.1

6.00 152

25.2

* Contact Duro-Last for additional thickness options.


TABLE 3. TYPICAL PHYSICAL PROPERTIES

Property

Test Method

Type VIII

Density

(nominal)

ASTM C 303

1.25 pcf

R-Value

(per inch)

@25°F
@40°F
@75°F

ASTM C 518

or

C 177

4.55
4.25
3.92

Compressive Strength

(10% deformation)

ASTM D 1621

13 – 18 psi

Flexural Strength

ASTM C 203

≥ 30 psi

Dimensional Stability

ASTM D 2126

≤ 2.0%

Water Vapor

Permeance

ASTM E 96

≤ 3.5 perm

Water Absorption

ASTM C 272

≤ 3.0%

Flame Spread

ASTM E 84

20

Smoke Developed

ASTM E 84

150 - 300