beautypg.com

VEGA VEGAPULS 56V User Manual

Page 59

background image

VEGAPULS 56V

59

• Enter here the checked product distance

and click to "Create new“.

Hence you cause the sensor to mark all ech-
oes in front of the level echo as false echoes.
This avoids that the sensor detects errone-
ously a false echo as level echo.

• Click to "Show echo curve“.

The echo curve and the false echo marking
are shown.

Set-up

You see that due to the strut, the false echo is
approx. 20 dB lower than the useful echo and
can therefore no more influence the measure-
ment.

• Quit the menu window

"Echo curve“ with

"Quit“.

With the menu point "

False echo storage“ in

the menu window "

Sensor optimisation“ you

cause the sensor electronics to mark false
echoes and to save in a database. The false
echoes are then treated different than the
useful echo.

• Click in the menu window "

Sensor optimisa-

tion“ to the menu point "False echo stor-
age
“.

• Click in the menu window "

False echo stor-

age“ to "Learn false echoes“. The small
window "

Learn false echoes“ opens.