2 adjustment with the pc on vegamet – VEGA VEGAPULS 56V User Manual
Page 49

VEGAPULS 56V
49
When the signal conditioning instruments are
exceptionally not pre-configured, start now
with the following section "
Configuration“ and
continue then with the adjustments in section
"Parameter adjustment“.
Configuration
Create new measurement loop
• Choose the menu "Configuration/Measure-
ment loop/New
“ and you are in the menu
window "Create new measurement loop -
Application“.
• Choose the parameter ("Level measure-
ment“, "gauge“ or "distance“) and the sen-
sor type ("Pulse-Radar“).
• Click to "Continue“.
Set-up
6.2 Adjustment with the PC on
VEGAMET
For connection of the PC to the signal condi-
tioning instrument the interface converter
VEGACONNECT 2 is required. The PC com-
municates via the interface converter with the
signal conditioning instrument and with the
connected sensor (s).
The individual adjustment steps are marked
in the following with a dot:
• Choose …
• Start …
• Click to …
Now start:
• Connect the standard plug of VEGACON-
NECT 2 (9-pole) with the interface COM 1
or COM 2 of your PC.
• Insert the two small pin plugs of VEGA-
CONNECT 2 into the CONNECT-sockets
on the front side of the signal conditioning
instrument.
• Now switch on the power supply of the
signal conditioning instrument.
After approx. 1␣ …␣ 2 minutes (self-check) the
measuring system is generally in operating
condition and displays measured values.
• Start the adjustment software VVO on your
PC.
Instruction before starting the
configuration:
The signal conditioning instruments are al-
ready configured according to the sensor
type ordered with the signal conditioning
instrument.
Generally you will therefore use a pre-config-
ured signal conditioning instrument. In the
following menu "
Configuration“, normally no
adjustments are necessary and you can
directly choose the menu "Parameter adjust-
ment“ on page 51.