VEGAMET 515V
1.4 Technical data
Power supply
Operating voltage
Unom = 20 … 53 V AC, 50/60 Hz
= 20 … 72 V DC
Power consumption
approx. 20 VA or approx. 15 W
Meas. data input
Number
2 inputs
Input type
active two-wire input, digital (VBUS) (sensor is
powered by VEGAMET)
Possible sensors (loop powered)
pressure transmitters, ultrasonic sensors,
radar sensors
Voltage
approx. 25 V DC
Current limitation
at approx. 7 W, short-circuit proof
Min. adjustment delta
2 % of sensor range (hydrostatic)
5 mm (ultrasonic, radar)
Connection cable
2-wire standard cable (screening recommen-
ded)
max. cable length
1000 m
max. resistance per wire
20
Ω
Correction signal input
Number
2 inputs
Function
switching signal to trigger corrections
or special relay modes via
external switching contact
Voltage
5 V (from instrument)
Current
5 mA
External cable resistance
≤
150
Ω
Current output
Number
3 outputs
Function
analogue output of the processing results
Range
individually adjustable in the range of 0 … 20 mA
Load
max. 500
Ω
Resolution
1 µA
Linearity error
0.05 % (relating to 20 mA)
Temperature error
0.05 %/10 K (relating to 20 mA)
Voltage output
Number
3 outputs
Function
analogue output of the processing results
Range
individually adjustable in the range of 0 … 10 V
Current
max. 1 mA
Resolution
0.5 mV
Linearity error
0.05 % (relating to 10 V)
Temperature error
0.06 %/10 K (relating to 10 V)
Product description