6 Configuration

6.1 Configuration measurement loop, two independent single

measurements

Configuration

The measurement loop configuration is usu-
ally provided as a factory setting. Should a
general modification of the measurement loop
configuration be necessary, "Reset to single
measurement“ or "Reset to linked application“
should be carried out first (with "Reset to
single measurement“ the VEGAMET is pre-
pared for configuration of two independent
single measurements. With "Reset to linked
application“ it is prepared for configuration of
linked applications). Only then can setting in
the menu items Application, Sensor type,
Mode and Option be modified. Proceed in
the menu items in the given sequence. The
adjustment or selection options always de-
pend on what was set in the previous menu
item. When e.g. in the menu item Application
"Level“ is set, only one sensor type suitable
for level detection can be selected in the
menu item "Sensor type“.

As soon as you have made an adjustment in
the menu item "Option“ and confirmed it, the
display shows the message: "TAG being
created!“.

In the following illustrations, different types of
applications are shown. In addition, you will
see which adjustments you have to carry out
in the menu items "Sensor type“ and "Mode“.

The menu item "Position D“ only appears
when in the menu item "Option“ either "Offset
correction“ or "Real value correction“ has
been set. The menu item "Position E“ only
appears when in the menu item "Option“
"Density correction“ has been set.

Confi-
gura-
tion

Config
inputs

Config
meas.
loop

TAG 1
Level

Appli-
cation

Level

Sensor
type

Hydro-
static

Mode

Stan-
dard

Option

no
option

Sensor
coordi-
nation

TAG-
name

TAG -
No. 1

Posi-
tion A

Input
no.1

Fault
signal

on

Param.
TAG-
No. 1

TAG -
No. 1
%

xx,x

off

Gauge
Distance

Pulse-echo
Pulse-radar

Tare

Fault
signal

on

Input
from

undef-
ined

Input
from

undef-
ined

Posi-
tion D

Input
no.4

Posi-
tionE

Input
no.4

TAG 2
Level

like TAG1

1)

1)

1)

1)

The settings in these menu items can only be
modified if a "Reset to single measurement“ was
carried out beforehand (under menu item "Addi-
tional functions“).