6 monitoring – VEGA VEGAMET 515V User Manual
Page 27
VEGAMET 515V
27
6.6 Monitoring
To activate the monitoring, the following
prerequirements must be met:
Meas.
value 50 %
High 5 %
Low –5 %
>55 %
Relay
deenergises
<45%
Configuration
• Choose in the menu item "
Input from
“ (un-
der the menu item "
Monitoring
“) input 4.
• Connect a key switch (opener) to input 4.
Confi-
gura-
tion
Config
inputs
Config
meas.
loop
TAG 1
Level
Appli-
cation
Level
Param.
TAG-
No. 1
TAG -
No. 1
%
xx,x
Moni-
toring
Input
from
Input
no.4
• Choose in the menu range "
Parameter
adjustment relay outputs
“ in the menu item
"
Mode
“ the mode "
Monitoring
“ for the se-
lected relay.
The selected relay becomes energised. By
pushing the key switch (opener opens) the
actual measured value is first of all frozen
and, derived from this, the relay deenergises
if this value is underrun (Low) or exceeded
(High). After a reset and repeated push of
the key switch, the actual measured value is
again frozen.
Param.
TAG-
No. 1
TAG -
No. 1
%
xx,x
Adjust-
ment
Signal
condit-
ioning
Out-
puts
Curr.
out-
puts
Volt
outputs
Relay
outputs
Relay
output
1
prop.
to
Per-
cent
Unit
0,0%
Mode
(moni-
toring)
Low
%
5,0
High
%
5,0
Monit.
to
Low &
High
If the monitoring function has to be deacti-
vated, monitoring must first be cancelled in
the menu item "
Mode
“. Then the allocation of
the correction input (input 4) must be can-
celled under the menu item "
Monitoring
“.