4 scaling, Parameter adjustment – VEGA VEGAMET 515V User Manual
Page 36
36
VEGAMET 515V
Set the number 1500 (with keys [+],
[–] and [OK]) in this menu item. This
corresponds to the level at 0 % (if
you want to have a lower resolution of
the meas. value indication, you can also set
150 or 15).
Set the number 4500 (with keys [+],
[–] and [OK]) in this menu item. This
corresponds to the level at 100 %.
Adjust the decimal point as shown
(with keys [+], [–] and [OK]).
Choose the term "Height“ in this
menu item (with keys [+], [–] and
[OK]).
If you have chosen "Height“ in the
previous menu item, you get a
choice of several units (mm, dm, cm,
m, yard…). Choose m (with the keys
[+], [–] and [OK]).
The scaled value is now shown in the
meas. value indication.
TAG -
No. 1
m
2,341
100 %
0 %
h=1.5 m
h=4.5 m
7.4 Scaling
The adjustments under scaling determine
which number values and which unit will actu-
ally be displayed on the measured value
indication (upper menu item). In the menu
items "0 % corresponds…“ and "100 % cor-
responds…“ you can enter with [+] or [–]
and [OK] values which should be displayed
at 0 % and at 100 % filling. In the menu item
"Decimal point…“ you determine the position
of the decimal point. In the next menu item
"prop. to…“ you get a choice of parameters:
push [+] or [–] to select percent, mass, vol-
ume, pressure etc. and save with [OK]. The
menu item "Unit…“ then serves up a corre-
sponding new choice, e.g. m, dm, cm, mm,
ft, yd and in, if you have selected the param-
eter "Height“ (compare chapter "8 Measuring
results and units“).
After a scaling, the requested output can be
assigned to the scaled value in the menu
range "Parameter adjustment outputs“ (menu
items "prop. to…“ and "Unit…“).
TAG-
No. 1
%
xx,x
Param.
TAG-
No. 1
Ad-
just-
ment
Sig-
nal
condi-
tioning
Scal-
ing
Unit
– –
prop.
to
unde
fined
Deci-
mal
point
888,8
100%
corres
ponds
1000
0%
corres
ponds
0
Meas.
value
indication
Scaling example
You have a raised tank and you want the
level to be indicated in meters with three
places after the decimal point.
0%
corres
ponds
1500
100%
corres
ponds
4500
Deci-
mal
point
8,888
2.341 m
Percent
Pressure
Mass
prop.
to
Height
Unit
m
dm
cm
….
Parameter adjustment