Installation guide, Network options – Veris Industries H8920-1 Install User Manual
Page 4
![background image](/manuals/260007/4/background.png)
Z202806-0H
PAGE 4
©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
07111
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
TM
H8920-1
INSTALLATION GUIDE
Indexing Option: Allows the node to access up to 63 H8036 meters for
viewing and archiving purposes only
Up to 63 H8036s
H8920-1 LON Node
LON Talk® Network
Modbus Network
Lon Talk®
Controller
NETWORK OPTIONS
Bound Option: For all applications requiring binding*
H8920-1 LON Node
H8036
H8036
Modbus Network
LON Talk® Network
Lon Talk®
Controller
*If employing the bound option, address each H8036 at 1.
Resetting the Energy Accumulator
To reset the Energy Accumulator nvoEgyWH, use the input network variable nviEgyClr
and follow this procedure:
1. Ensure that nviEgyClr.state > 0 & nviEgyClr.value > 0. Default is {1,1}.
2. Set nviEgyClr.state = 0 & nviEgyClr.value = 0.
3. Set nviEgyClr.state = 1 & nviEgyClr.value = 1.
At step 3, the H8920-1 issues an energy accumulator reset command to the H8036.
Once cleared, the meter will continue to count kWh from zero until another reset is
commanded.
Resetting the Average/Minimum/Maximum Power Variables
Reset the power variables (nvoAvePower, nvoMinPower, and nvoMaxPower) to
instantaneous power by following this procedure:
1. Ensure that nviPwrClr.state > 0 & nviPwrClr.value > 0Default is {1,1}.
2. Set nviPwrClr.state = 0 & nviPwrClr.value = 0.
3. Set nviPwrClr.state = 1 & nviPwrClr.value = 1.
The H8920-1 issues the Clear Power Variables command to the H8036 in Step 3.
Once cleared, the meter will monitor min/max/average power until another reset is
commanded. Note that all three variables are cleared in one command.
Node Identification
Wink: The LON Node will light its service LED for 5 seconds in response to a WINK
command.
Service Pin: A service pushbutton is provided for this method of identification.
(See Product Diagram section).
Neuron ID: The Neuron ID is located on a label on the back of the device. It can be
written down or peeled off as a removable sticker with bar code for easy insertion to
your network.
Program ID
The standard program ID for this product is 90:00:14:8A:0D:02:04:01