Indexing Option: Allows the node to access up to 63 H8036 meters for

viewing and archiving purposes only

Up to 63 H8036s

H8920-1 LON Node

LON Talk® Network

Modbus Network

Lon Talk®

Controller

NETWORK OPTIONS

Bound Option: For all applications requiring binding*

H8920-1 LON Node

H8036

H8036

Modbus Network

LON Talk® Network

Lon Talk®

Controller

*If employing the bound option, address each H8036 at 1.

Resetting the Energy Accumulator

To reset the Energy Accumulator nvoEgyWH, use the input network variable nviEgyClr
and follow this procedure:

1. Ensure that nviEgyClr.state > 0 & nviEgyClr.value > 0. Default is {1,1}.

2. Set nviEgyClr.state = 0 & nviEgyClr.value = 0.

3. Set nviEgyClr.state = 1 & nviEgyClr.value = 1.

At step 3, the H8920-1 issues an energy accumulator reset command to the H8036.
Once cleared, the meter will continue to count kWh from zero until another reset is
commanded.

Resetting the Average/Minimum/Maximum Power Variables

Reset the power variables (nvoAvePower, nvoMinPower, and nvoMaxPower) to
instantaneous power by following this procedure:

1. Ensure that nviPwrClr.state > 0 & nviPwrClr.value > 0Default is {1,1}.

2. Set nviPwrClr.state = 0 & nviPwrClr.value = 0.

3. Set nviPwrClr.state = 1 & nviPwrClr.value = 1.

The H8920-1 issues the Clear Power Variables command to the H8036 in Step 3.
Once cleared, the meter will monitor min/max/average power until another reset is
commanded. Note that all three variables are cleared in one command.

Node Identification

Wink: The LON Node will light its service LED for 5 seconds in response to a WINK
command.

Service Pin: A service pushbutton is provided for this method of identification.
(See Product Diagram section).

Neuron ID: The Neuron ID is located on a label on the back of the device. It can be
written down or peeled off as a removable sticker with bar code for easy insertion to
your network.

Program ID

The standard program ID for this product is 90:00:14:8A:0D:02:04:01