Bacnet programming information (cont.) – Veris Industries E50H5 Install User Manual
Page 24

ZL0071-0D
Page 24 of 28
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
#
Object_Name
Description
R/W
NV
Units
Range
Additional information
AI26
kVAh
Apparent Energy
Consumption
R
NV
kVAh
0 - 3.4+E38
The UNITS property of object AI26 reports that these units
are kWh because there is no unit type in the BACnet
standard for kVAh.
AI27
kVARh
Reactive Energy
Consumption
R
NV
kVARh
0 - 3.4+E38
The UNITS property of object AI27 reports that these units
are kWh because there is no unit type in the BACnet
standard for kVARh.
AI28
kVA_A
Apparent Power
Phase A
R
kVA
0 - Max_Power (AI45)
AI29
kVA_B
Apparent Power
Phase B
R
kVA
0 - Max_Power (AI45)
AI30
kVA_C
Apparent Power
Phase C
R
kVA
0 - Max_Power (AI45)
AI31
KVAR_A
Reactive Power
Phase A
R
kVAR
0 - Max_Power (AI45)
AI32
KVAR_B
Reactive Power
Phase B
R
kVAR
0 - Max_Power (AI45)
AI33
KVAR_C
Reactive Power
Phase C
R
kVAR
0 - Max_Power (AI45)
AI34
KW_Present_
Demand
Total Real Power
Present Demand
R
kW
0 - Max_Power (AI45)
AI35
KVAR_Present_
Demand
Total Reactive Power
Present Demand
R
kVAR
0 - Max_Power (AI45)
AI36
KVA_Present_
Demand
Total Apparent Power
Present Demand
R
kVA
0 - Max_Power (AI45)
AI37
KW_Max_
Demand
Total Real Power
Maximum Demand
R
NV
kW
0 - Max_Power (AI45)
This retains the largest value measured for Total Real
Power Demand (AI34) for any single demand interval
since the Max Demand was last explicitly reset via
AV1 (this is also reset when the demand interval is
changed).
AI38
KVAR_Max_
Demand
Total Reactive Power
Maximum Demand
R
NV
kVAR
0 - Max_Power (AI45)
This retains the largest value measured for Total Reactive
Power Demand (AI35) for any single demand interval
since the Max Demand was last explicitly reset via
AV1 (this is also reset when the demand interval is
changed).
AI39
KVA_Max_
Demand
Total Apparent Power
Maximum Demand
R
NV
kVA
0 - Max_Power (AI45)
This retains the largest value measured for Total Apparent
Power Demand (AI36) for any single demand interval
since the Max Demand was last explicitly reset via
AV1 (this is also reset when the demand interval is
changed).
AI40
E50H2: Pulse
Count
E50H5: Pulse_
Count_1
E50H2: Pulse Count
E50H5: Pulse Count
#1
R
NV
#
0 - 4294967040
Running count of contact closures on Pulse1 input since
last reset. Write 16498 (0x4072) to the Present_Value
property of Analog_Value object AV1 to reset both
Pulse Counters to 0.
AI41
E50H2: Reserved
E50H5: Pulse_
Count_2
E50H2: Reserved
E50H5: Pulse Count
#2
R
NV
#
0 - 4294967040
E50H2: Reserved
E50H5: Pulse Count 2; Running count of contact closures
on Pulse2 input since last reset. Write 16498 (0x4072)
to the Present_Value property of Analog_Value object
AV1 to reset both Pulse Counters to 0.
AI42
KWH_A
Real Energy
Consumption
Phase A
R
NV
kWh
0 - 3.4+E38
AI43
KWH_B
Real Energy
Consumption
Phase B
R
NV
kWh
0 - 3.4+E38
BACnet Programming Information (cont.)