Bacnet default settings – Veris Industries E50H5 Install User Manual
Page 17

ZL0071-0D
Page 17 of 28
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2, E50H5
TM
Setting
Default Value*
BACnet Object
Setup Password
00000
n/a
Reset Password
00000
n/a
System Type
40 (3 + N) Wye
AV2
CT Primary Ratio
100A
AV3
CT Secondary Ratio
1V
AV4
PT Ratio
1:1 (none)
AV5
System Voltage
600 V L-L
AV6
Max. Theoretical Power
Calculated from AV2, AV3, AV5 & AV6 (with all default settings, this would be
103.92 kW)
AI45
Display Mode
1 (IEEE Units)
AV7
Phase Loss Voltage Threshold 10% of System Voltage
AV8
Phase Loss Voltage Threshold 25% Phase to Phase Imbalance
AV9
Demand: number of
subintervals per interval
1 (block mode)
AV10
Demand: sub-interval length 900 sec (15 min)
(AV11 default value is 90000 [1/100 seconds])
AV11
BACnet MAC Address
001
n/a
BACnet MS/TP Baud Rate
76.8 kBaud
n/a
BACnet MS/TP Max_Master
127
Device
BACnet Device_ID
Pseudo-random value
from 1,000,000 to 3,097,151
Device
BACnet Device Location
Installed location not yet identified
Device
Trend_Log Object 1
Log_Device_Object_
Property **
AI1 (Real Energy)
TL1
Trend_Log Object 2
Log_Device_Object_
Property **
AI27 (Reactive Energy)
TL2
Trend_Log Object 3
Log_Device_Object_
Property **
AI34 (Total Real Present Demand)
TL3
* Default values are preset at the factory. Once changed, there is no way to automatically reset defaults. They must be restored individually. The baud rate and
MAC address are set through the user-interface screens, and the others are set by re-writing each Object (see BACnet Programming Information section, next
page).
** These values are available only on the E50H5. The E50H2 does not support the data logging functions.
BACnet Default
Settings