Installation Guide

Power Monitoring

E50H2, E50H5

TM

Setting

Default Value*

BACnet Object

Setup Password

00000

n/a

Reset Password

00000

n/a

System Type

40 (3 + N) Wye

AV2

CT Primary Ratio

100A

AV3

CT Secondary Ratio

1V

AV4

PT Ratio

1:1 (none)

AV5

System Voltage

600 V L-L

AV6

Max. Theoretical Power

Calculated from AV2, AV3, AV5 & AV6 (with all default settings, this would be

103.92 kW)

AI45

Display Mode

1 (IEEE Units)

AV7

Phase Loss Voltage Threshold 10% of System Voltage

AV8

Phase Loss Voltage Threshold 25% Phase to Phase Imbalance

AV9

Demand: number of

subintervals per interval

1 (block mode)

AV10

Demand: sub-interval length 900 sec (15 min)

(AV11 default value is 90000 [1/100 seconds])

AV11

BACnet MAC Address

001

n/a

BACnet MS/TP Baud Rate

76.8 kBaud

n/a

BACnet MS/TP Max_Master

127

Device

BACnet Device_ID

Pseudo-random value

from 1,000,000 to 3,097,151

Device

BACnet Device Location

Installed location not yet identified

Device

Trend_Log Object 1

Log_Device_Object_

Property **

AI1 (Real Energy)

TL1

Trend_Log Object 2

Log_Device_Object_

Property **

AI27 (Reactive Energy)

TL2

Trend_Log Object 3

Log_Device_Object_

Property **

AI34 (Total Real Present Demand)

TL3

* Default values are preset at the factory. Once changed, there is no way to automatically reset defaults. They must be restored individually. The baud rate and
MAC address are set through the user-interface screens, and the others are set by re-writing each Object (see BACnet Programming Information section, next
page).
** These values are available only on the E50H5. The E50H2 does not support the data logging functions.

BACnet Default
Settings