Bacnet programming information (cont.) – Veris Industries E50H5 Install User Manual

Page 22

background image

ZL0071-0D

Page 22 of 28

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 10131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E50H2, E50H5

TM

#

Name

Description R/W

NV

Units

Range

Factory

Default

Value

Additional information

AV6

System_

Voltage

System

Voltage

R/W

NV

Volts

from 82 (times

the PT_Ratio

in AV5) to

660 (times

the PT_Ratio

in AV5 -

absolute

limits are

82-32000)

600

System Voltage – This voltage is Line to Line unless in System Type 10 (in object AV2), in

which case it is Line to Neutral. This value is used to by the meter to calculate the full

scale power for the analog outputs and pulse configuration (see below), and as full

scale for phase loss (in object AV8). Do not set the meter to voltages outside the range

of 82-660 volts times the PT Ratio in object AV5.

AV7

Display_

Units

Display Units R/W

NV

n/a

0,1

1

Display Units: 0 = IEC (U, V, P, Q, S), 1 = IEEE (default: VLL, VLN, W, VAR, VA)

AV8

Phase_Loss_

Voltage_

Threshold

Phase Loss

Voltage

Threshold

R/W

NV

Percent

1-99

10

Phase Loss Voltage Threshold in percent of System Voltage (in object AV6). Default is

10 (10%). Any phase (as configured in AV2) whose level drops below this threshold

triggers a Phase Loss alert - i.e. if the System voltage is set to 480 V L-L, the L-N

voltage for each phase should be 277 V. When the threshold is set to 10%, if any phase

drops more than 10% below 277 V, (less than 249 V), or if any L-L voltage drops more

than 10% below 480 V (less than 432 V) the corresponding phase loss alarm bit will

be true.

AV9

Phase_Loss_

Imbalance_

Threshold

Phase Loss

Imbalance

Threshold

R/W

NV

Percent

1-99

25

Phase Loss Imbalance Threshold in Percent. Default is 25% phase to phase difference.

For a 3-phase Y (3 + N) system type (40 in object AV2), both Line to Neutral and Line

to Line voltages are tested. In a 3-phase ∆ System type (31 in object AV2), only Line to

Line voltages are examined. In a single split-phase (2 + N) system type (12 in object

AV2), only the line to neutral voltage are compared.

AV10 Subintervals

Number

Subintervals

Per Demand

Interval

R/W

NV

1-6

1

Number of Sub-Intervals per Demand Interval. Sets the number of sub-intervals that

make a single demand interval. For block demand, set this to 1. Default is 1. When

Sub-Interval Length (in object AV11) is set to 0 (sync-to-comms mode), the meter

ignores this value.

AV11 Subinterval_

Length

Subinterval

Length

R/W

NV

hundreths

of a

second

0,

10-32767

90000

Sub-Interval Length in hundredths of a second. For sync-to-comms mode, which allows

manual triggerring of demand intervals and the logging of another Trend_Log record,

set this value to 0 and write 21211 to the reset register (object AV1) each time the

sub-interval must be externally reset. Default is 90000 (15 minutes). This variable is

tied directly to the Log_Interval property of all three Trend_Log objects (their value

is always the same as this one). Changing any of these four properties changes all of

them.

Trend_Log values are only used on the E50H5 model.