UI for Setup (cont.)
Next
Set Passwords:
SETUP - The Password to enter the SETUP menu.
RESET - The Password to enter the RESET menu.
RESET
--------
00000
SPASS
Setup
Passwords
SETUP
--------
00000
Back
Next
SDMND
INTRV
--------
6
5
4
3
2
1
Demand
SEC
--------
00900
Back
Set Demand Interval:
INTRV - The number of Sub-Intervals (1 to 6) in a
Demand Interval
. Default is 1 (block demand).
SEC - Sub-Interval length in seconds. Default is
900 (15 minutes). Set to 0 for external sync-to-
comms.
Next
S DIS
Display
Units
UNITS
--------
IEEE
IEC
Back
Set Display Units: +/- to switch between:
IEEE – VLL VLN W VAR VA Units.
IEC - U V P Q S Units.
To Setup p. 1 “S PWR”
SPLOS
Back
IMBAL
--------
0.25
Next
VOLTS
--------
0.10
Set Phase Loss:
VOLTS - Phase Loss Voltage: The fraction of the system
voltage below which Phase Loss Alarm is on. For system
types with neutral, the Line to Neutral voltage is also
calculated and tested. If the System Voltage is 600 and the
fraction is set to 0.10, then the Phase Loss threshold will be
60 volts.
IMBAL - Phase Loss Imbalance: The fractional difference
in Line to Line voltages above which Phase Loss Alarm is
on. For system types with neutral, the Line to Neutral
voltages are also tested. For system types 1+N (10) and 2
(11) , imbalance is not tested.
Phase
Loss
To Setup page 1 “S BAC”