In the example below we use a control panel VMB4PD of which 8 controls are linked to a temperature sensor.

The labels on the display are assigned as indicated (refer to the manual of the VMB4PD):


The labels on the display for the second page are assigned as indicated:


Remotely control comfort mode

With the upper left button of the control panel the temperature sensor is set to comfort mode.



1. Remember the address of the sensor module to

reinstate it later.

2. Set the address of the sensor module to ‘F1’.

The comfort and day LEDs are flashing to indicate
learning mode for pushbuttons that place the
module in comfort mode.

Remark:
When multiple sensor modules needs to react to
the same pushbutton, remember their addresses
and set them also to ‘F1’.


3. Press and hold the ‘Comfort’ pushbutton

(at least 1 second) until its indication LED starts
flashing.

Remark:
As long as the pushbutton is pressed, the LEDs on
the sensor module will be off. This to confirm that
the pushbutton is assigned.

4. Repeat step 3 in case other pushbuttons must set

the sensor module in comfort mode.

5. Reinstate the address of the sensor module(s) to

its (their) original value.




ADDR = F1

 

 

Comfort Day
Night Anti-freeze

 

Heating Lock
Cooling Unlock

 

Comfort Day
Night Anti-freeze