6 cooling capacities - models, Dhe/dhg 036 - 105°f - 115ºf, Table 6: cooling capacities - models dhe/dhg 036 – York D2HE/D2HG060 User Manual

Page 8: Nominal rating all sensible capacity

background image

036-21216-003-A-0204

8

Unitary Products Group

TABLE 6: COOLING CAPACITIES - MODELS DHE/DHG 036 -

105°F - 115ºF

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

105°F

TOTAL

CAP.

1

MBH

POWER

INPUT

2

SENSIBLE CAPACITY

3

ENTERING DRY BULB, °F

CFM

WB

°F

86

83

80

77

74

71

68

1500

72

47.6

3.65

32.3

27.8

23.3

18.9

14.4

#N/A

#N/A

67

42.5

3.56

39.0

34.5

30.0

25.6

21.1

16.6

12.1

62

38.0

3.49

38.0

38.0

36.6

32.1

27.6

23.1

18.7

57

37.4

3.54

37.4

37.4

37.4

32.9

28.5

24.0

19.5

1350

72

46.5

3.62

29.7

25.8

21.8

17.8

13.8

#N/A

#N/A

67

41.6

3.53

36.0

32.0

28.0

24.0

20.1

16.1

12.1

62

37.1

3.46

37.1

36.6

34.1

30.1

26.1

22.2

18.2

57

36.5

3.52

36.5

36.5

35.2

31.2

27.2

23.3

19.3

1200

72

45.4

3.60

27.2

23.7

20.2

16.7

12.2

#N/A

#N/A

67

40.6

3.51

33.0

29.5

26.0

22.5

19.0

15.5

12.0

62

36.2

3.44

36.2

35.2

31.7

28.2

24.7

21.2

17.7

57

35.7

3.49

35.7

35.7

33.0

29.5

26.0

22.5

19.0

1050

72

43.2

3.57

24.6

21.6

18.5

12.5

#N/A

#N/A

67

38.7

3.48

29.9

26.9

23.8

20.8

17.8

14.7

11.7

62

34.5

3.41

33.9

32.1

29.0

26.0

23.0

19.9

16.9

57

34.0

3.47

34.0

32.9

30.3

27.2

24.2

21.2

18.1

900

72

41.1

3.54

22.0

19.4

16.8

14.3

11.7

#N/A

#N/A

67

36.7

3.45

26.8

24.2

21.7

19.1

16.5

14.0

11.4

62

32.8

3.39

31.5

28.9

26.4

23.8

21.2

18.7

16.1

57

32.3

3.44

32.3

30.1

27.5

24.9

22.4

19.8

17.2

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

115°F

TOTAL

CAP.

MBH

POWER

INPUT

SENSIBLE CAPACITY

ENTERING DRY BULB, °F

CFM

WB

°F

86

83

80

77

74

71

68

1500

72

43.6

3.85

30.4

26.0

21.5

17.0

12.5

#N/A

#N/A

67

39.3

3.76

37.8

33.3

28.8

24.3

19.9

15.4

10.9

62

34.8

3.67

34.8

34.8

34.4

29.9

25.4

20.9

16.5

57

34.9

3.73

34.9

34.9

34.9

30.5

26.0

21.5

17.0

1350

72

42.9

3.83

28.0

24.0

20.0

16.0

12.0

#N/A

#N/A

67

38.6

3.74

34.8

30.8

26.8

22.8

18.8

14.9

10.9

62

34.2

3.66

34.2

34.0

32.0

28.0

24.0

20.0

16.0

57

34.3

3.72

34.3

34.3

32.9

28.9

24.9

21.0

17.0

1200

72

42.2

3.82

25.5

22.0

18.5

15.0

11.5

#N/A

#N/A

67

37.9

3.73

31.8

28.3

24.8

21.3

17.8

14.3

10.8

62

33.6

3.64

33.6

33.1

29.6

26.1

22.6

19.1

15.6

57

33.7

3.70

33.7

33.7

30.9

27.4

23.9

20.4

16.9

1050

72

40.1

3.78

22.9

19.9

16.9

13.8

10.8

#N/A

#N/A

67

36.1

3.69

28.7

25.7

22.6

19.6

16.6

13.5

10.5

62

32.0

3.61

31.6

30.0

27.0

23.9

20.9

17.9

14.9

57

32.1

3.67

32.1

30.9

28.2

25.1

22.1

19.1

16.0

900

72

38.0

3.75

20.4

17.8

15.2

12.7

10.1

#N/A

#N/A

67

34.2

3.66

25.6

23.0

20.4

17.9

15.3

12.7

10.2

62

30.3

3.58

29.5

26.9

24.4

21.8

19.2

16.7

14.1

57

30.4

3.64

30.4

28.0

25.4

22.9

20.3

17.7

15.2

1.

These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance

Table, multiply this value by 3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit

2.

These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor

power input is 0.36kW. Refer to Tables 10 and 11 for the kW of the supply air blower motor.

3.

These capacities are gross ratings. For net capacity, determine the kW of the supply air blower from Tables 10 and 11, multiply this value

by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.

NOMINAL RATING

ALL SENSIBLE CAPACITY