TABLE 2: CAPACITY RATINGS - COOLING / GAS HEATING

MODEL

ARI RATINGS

1

GAS HEAT CAPACITY

COOLING CAPACITY

80 / 67-95°F

SOUND

RATING

2

(dBels)

INPUT

(MBH)

DOE

OUTPUT

(MBH)

AFUE

3

(%)

S.S.E.

4

(%)

S.E.

5

(%)

TEMP. RISE

(°F)

GAS

LINE SIZE

(in. O.D.)

MBH

SEER

6

EER

7

DHG036N040

42.5

12.25

11.1

86

50

40

80.0

81.6

77.3

15-45

1/2

DHG036N079

42.5

12.25

11.1

86

100

79

80.5

80.8

77.9

40-70

1/2

DHG048N060

46.5

13.20

11.40

87

75

59

80.9

81.6

77.3

25-55

1/2

DHG048N099

125

99

80.3

80.6

77.9

45-75

1/2

DHG060N079

57.0

12.20

10.60

86

100

79

80.5

80.8

73.6

25-55

1/2

DHG060N099

125

99

80.3

80.6

77.9

35-65

1/2

1.

Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/240.

2.

Rated in accordance with ARI Standard 110, utilization range “A”.

3.

AFUE = Annual Fuel Utilization Efficiency - determined in accordance with DOE test procedure.

4.

S.S.E. = Steady State Efficiency. (Percent Output)

5.

S.E. = California Seasonal Efficiency - determined in accordance with test procedures as specified by the State of California
Energy Commission. Furnaces are available with a low NOx accessory.

6.

SEER = Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling
divided by the total electric power input in watt-hours during the same period.

7.

EER = Energy Efficiency Ratio - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts at any given set of
rating conditions, expressed in BTUH per watt (BTUH/watt).

TABLE 3: SOUND POWER RATINGS

1

UNIT

SIZE

CFM

ESP

BLOWER

SOUND POWER (dB 10

-12

Watts)

OCTAVE BAND CENTERLINE FREQUENCY (Hz)

SWL

dB(A)

dBA

@ 10 ft.

2

IWG

SPEED

kW

63

125

250

500

1000

2000

4000

8000

036

1200

0.60

LOW

0.60

84

84

74

67

69

62

57

52

74

41

048

1600

0.55

HIGH

0.80

85

85

75

68

70

63

58

53

75

42

060

2000

0.45

HIGH

1.00

86

86

76

69

71

64

59

54

76

43

1.

These values have been accessed using a model of sound propagation from a point source into the hermispheric free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacturer has no way of knowing the details of each system. This constitutes an exception to any specification or guarantee
requiring a dBA value or sound data in any other form than sound power level ratings.

2.

At a distance of 10 feet from the blower.

TABLE 4: PHYSICAL DATA - BASIC UNIT

MODELS

DHE/DHG

036

048

060

EVAPORATOR

BLOWER

CENTRIGUGAL BLOWER (Dia. x Wd. in.)

FAN MOTOR HP (BELT-DRIVE)

12 x 10

1.5

12 x 10

1.5

12 x 10

1.5

EVAPORATOR

COIL

ROWS DEEP

FINS PER INCH

FACE AREA (Sq. Ft.)

4

13

4.3

4

13

5.1

4

13

5.1

CONDENSER

FAN

PROPELLER DIA. (in.)

FAN MOTOR HP

NOM. CFM TOTAL

24

1/2

4,500

24

1/2

4,200

24

1/2

4,200

AIR

FILTERS

1

QUANITY PER UNIT (15” X 20” X 1”)

QUANTITY PER UNIT (14” X 25” X 1”)

TOTAL FACE AREA (square feet)

2

1

6.6

2

1

6.6

2

1

6.6

SYSTEM

CHARGE

REFRIGERANT 22 (pounds/ounces)

10/8

10/*4

10/14

COMPRESSOR

QUANTITY PER UNIT (Hermetic Type)

1 / Recpt.

1 / Recpt.

1/Recpt.

1.

Filter racks are adapted for 1” or 2” thick filters.