TABLE 5: COOLING CAPACITIES - MODELS DHE/DHG 036 -

85°F - 95ºF

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

85°F

TOTAL

CAP.

1

MBH

POWER

INPUT

2

SENSIBLE CAPACITY

3

ENTERING DRY BULB, °F

CFM

WB

°F

86

83

80

77

74

71

68

1500

72

55.2

3.18

35.2

30.7

26.2

21.8

17.3

#N/A

#N/A

67

49.1

3.13

41.7

37.2

32.8

28.3

23.8

19.4

14.9

62

44.7

3.05

44.7

43.6

39.1

34.6

30.1

25.7

21.2

57

42.4

3.05

42.4

42.4

42.4

37.9

33.4

29.0

24.5

1350

72

55.2

3.18

35.2

30.7

26.2

21.8

17.3

#N/A

#N/A

67

49.1

3.13

41.7

37.2

32.8

28.3

23.8

19.4

14.9

62

44.7

3.05

44.7

43.6

39.1

34.6

30.1

25.7

21.2

57

42.4

3.05

42.4

42.4

42.4

37.9

33.4

29.0

24.5

1200

72

51.9

-3.15

30.0

26.5

23.0

19.5

16.0

#N/A

67

46.1

3.10

35.7

32.2

28.7

25.2

21.7

18.2

14.7

62

42.0

3.02

41.2

37.7

34.2

30.7

27.2

23.7

20.2

57

39.8

3.03

39.8

39.8

37.3

33.8

30.3

26.8

23-3

1050

72

49.4

3.12

27.3

24.3

21.2

182

15.2

#N/A

67

43.9

3.07

32.6

29.6

26.5

23.5

20.5

17.4

14.4

62

40.0

2.99

37.7

34.7

31.6

28.6

25.6

22.5

19.5

57

37.9

3.00

37.9

37.0

34.5

31.4

28.4

25.4

22.3

900

72

46.9

3.09

24.6

22.1

19.5

16.9

14.4

#N/A

67

41.7

3.04

29.5

26.9

24.4

21.8

19.2

16.7

14.1

62

38.0

2.96

34.2

31.6

29.1

26.5

23.9

21.4

18.8

57

36.0

2.97

36.0

34.2

31.7

29.1

26.5

24.0

21.4

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

95°F

TOTAL

CAP.

MBH

POWER

INPUT

SENSIBLE CAPACITY

ENTERING DRY BULB, °F

CFM

WB

°F

86

83

80

77

74

71

68

1500

72

51.5

3.44

34.1

29.7

25.2

20.7

16.2

#N/A

#N/A

67

45.8

3.35

40.2

35.7

31.3

26.8

22.3

17.8

13.4

62

41.2

3.30

41.2

41.2

38.8

34.3

29.8

25.3

20.9

57

39.9

3.35

39.9

39.9

39.9

35.4

31.0

26.5

22.0

1350

72

50.0

3.41

31.5

27.5

23.6

19.6

15.6

#N/A

#N/A

67

44.5

3.32

37.2

33.2

29.2

25.3

2 13

17.3

13.3

62

40.0

3.27

40.0

39.2

36.3

32.3

28.3

24.3

20.3

57

38.8

3.32

38.8

38.8

37.5

33.5

29.6

25.6

21.6

1200

72

48.6

3.38

28.9

25.4

21.9

18.4

14.9

#N/A '

#N/A

67

43.2

3.29

34.2

30.7

27.2

23.7

20.2

16.7

13.2

62

38.9

3.23

38.9

37.2

33.7

30.2

26.7

23.2

19.8

57

37.6

3.29

37.6

37.6

35.1

31.6

28.1

24.6

21.1

1050

72

46.4

3.36

26.2

23.2

20.2

17.2

14.1

#N/A

#N/A

67

41.2

3.27

31.1

28.1

25.0

22.0

19.0

16.0

12.9

62

37.1

3.21

36.2

34.1

31.1

28.0

25.0

22.0

18.9

57

35.9

3.27

35.9

34.9

32.3

29.3

26.3

23.2

20.2

900

72

44.2

3.34

23.6

21.0

18.4

15.9

13.3

#N/A

#N/A

67

39.3

3.25

28.0

25.4

22.9

20.3

17.7

15.2

12.6

62

35.4

3.20

33.5

30.9

28.4

25.8

23.2

20.7

18.1

57

34.2

3.25

34.2

32.1

29.5

27.0

24.4

21.8

19.3

1.

These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply

this value by 3.415 MBH / KW to determine the motor heat, and deduct this heat from the gross capacity of the unit

2.

These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input

is 0.36kW. Refer to Tables 10 and 11 for the kW of the supply air blower motor.

3.

These capacities are gross ratings. For net capacity, determine the kW of the supply air blower from Tables 10 and 11, multiply this value by 3.415

MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.

NOMINAL RATING

ALL SENSIBLE CAPACITY