beautypg.com

Table 13: motor and drive data - belt-drive blower, Table 14: electrical data - basic unit, 13 motor and drive data - belt-drive blower 14 – York D2HE/D2HG060 User Manual

Page 14

background image

036-21216-003-A-0204

14

Unitary Products Group

TABLE 13: MOTOR AND DRIVE DATA - BELT-DRIVE BLOWER

MODEL

BLOWER

RANGE

(RPM)

MOTOR

1

ADJUSTABLE

MOTOR PULLEY

FIXED

BLOWER PULLEY

BELT

HP

RPM

FRAME

SIZE

SERVICE

FACTOR

PITCH

DIA.

(in.)

BORE

(in.)

PITCH

DIA.

(in.)

BORE

(in.)

PITCH

LENGHT

(in.)

DESIG-

NATION

DHE/DHG 036

780 - 1120

1

1/

2

1,725

56

1.15

2.4 - 3.4

7/

8

5.7

1

37.3

A36

DHE/DHG048

790 - 1,120

1

1/

2

1,725

56

1.15

2.4 - 3.4

7/

8

5.7

1

37.3

A36

DHE/DHG060

850 - 1,220

1

1/

2

1,725

56

1.15

2.4 - 3.4

7/

8

5.2

1

37.3

A36

1.

All motors have solid bases and are inherently protected. These motors can be selected to operate into their service factor
because they are located in the moving air, upstream of any heating device

TABLE 14: ELECTRICAL DATA - BASIC UNIT

MODEL

DHE/

DHG

POWER

SUPPLY

VOLTAGE

LIMITATIONS

1

COMPRESSOR

COND.

FAN

MOTOR

FLA

SUPPLY

AIR

AMPACITY

AMPS

TOTAL

UNIT

AMPACITY

AMPS

MAX.

FUSE
SIZE

2

AMPS

MAX.

HACR

BREAKER

SIZE

AMPS

MIN.

MAX.

RLA

LRA

036

208/230-3-60

187

253

14.1

110

2.3

5.3

25.2

35

35

460-3-60

414

504

7.1

54

1.4

3.1

13.3

20

20

048

208/230-3-60

187

253

10.0

110.0

2.3

5.2

23.9

35

35

460-3-60

414

504

5.2

54.0

1.4

2.6

12.4

15

15

060

208/230-3-60

187

253

16.0

137.0

2.3

6.0

28.3

40

40

460-3-60

414

504

8.3

69.0

1.4

3.0

14.8

20

20

1.

Rated in accordance with ARI Standard 110, utilization range “A”..

2.

Dual element, time delay type.

This manual is related to the following products: