036-21216-003-A-0204

Unitary Products Group

15

TABLE 15: ELECTRICAL DATA - COOLING/ELECTRIC HEAT DHE036 & 048

MODEL

DHE

POWER

SUPPLY

HEATER

ACCESSORY

MODEL

NUMBER

SUPPLY

AIR

BLOWER

MOTOR

FLA

ELECTRIC HEATERS

TOTAL

UNIT

AMPACITY

AMPS

MAX.

FUSE
SIZE

1

AMPS

MAX.

SIZE

HACR

2

AMPS

kW

STAGES

TOTAL

AMPS

036

208-3-60

2CE04500525

3

5.3

4.0

1

11.0

25.2

35

35

2CE04500725

4

5.6

1

15.6

26.2

35

35

2CE04501025

8.0

1

22.1

34.2

35

35

2CE04501525

11.9

2

33.1

48.1

50

50

2CE04502025

15.9

2

44.2

61.9

70

70

230-3-60

2CE04500525

4

5.3

5.3

1

12.7

25.2

35

35

2CE04500725

4

7.5

1

18.0

29.2

35

35

2CE04501025

10.6

1

25.5

38.5

40

40

2CE04501525

15.9

2

38.2

54.4

60

60

2CE04502025

21.2

2

51.0

70.4

80

80

460-3-60

2CE04500746

4

3.1

6.8

1

8.2

14.1

20

15

2CE04501046

4

10.1

1

12.1

19.1

20

20

2CE04501546

4

13.6

1

16.4

24.3

25

25

2CE04502046

4

19.5

2

23.5

33.2

35

35

048

208-3-60

2CE04500525

4

6.0

4.0

1

11.0

26.0

35

35

2CE04500725

4

5.6

1

15.6

26.9

35

35

2CE04501025

8.0

1

22.1

35.3

35

35

2CE04501525

11.9

2

33.1

48.8

50

50

2CE04502025

15.9

2

44.2

62.7

70

70

230-3-60

2CE04500525

4

6.0

5.3

1

12.7

26.0

35

35

2CE04500725

4

7.5

1

18.0

30.1

35

35

2CE04501025

10.6

1

25.5

39.4

40

40

2CE04501525

15.9

2

38.2

55.3

60

60

2CE04502025

21.2

2

51.0

71.2

80

80

460-3-60

2CE04500746

4

3.0

6.8

1

8.2

14.0

15

15

2CE04501046

4

10.1

1

12.1

18.9

20

20

2CE04501546

4

13.6

1

16.4

24.2

25

25

2CE04502046

4

19.5

2

23.5

33.1

35

35

1.

Dual element, time delay type.

2.

Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.

3.

These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), refer to Table 17
for fuse block accessories available for field installation.

4.

These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (e.g. Chicago), refer to Table 17
for fuse block accessories available for field installation.

TABLE 16: ELECTRIC HEAT CORRECTION

FACTORS (DHE048)

NOMINAL VOLTAGE

VOLTAGE

kW CAP

MULTIPLIER

208

208

1.00

240

230

0.92

480

460

0.92

600

575

0.92

TABLE 17: FUSE BLOCK ACCESSORY

2FB04700425

208/240 Volts

2FB04700546

460 Volts