4 single phase speed counter – Toshiba Programmable Logic Controller V200 User Manual

Page 99

background image

Page 91

5.4 Single Phase Speed Counter

This function counts the number of changes of the count input from OFF to ON during the every specified sampling
time. The count value in a sampling time is stored in the hold value register. This counter operation is enabled while
the soft-gate is ON. When the soft-gate is OFF, the hold value is cleared to 0. The setting range of the sampling time
is 1 to 1000 ms (1 ms units). The count value range is H0000 0000 to HFFFF FFFF (32-bit).

The function selection is done through configuration register1.

Function

Register/device

Remarks

Channel 1

Channel 2

Count input

IP 1 (X000)

IP 2 (X001)

Sampling time

MW12

MW14

Data range: 1 to 1000

Hold value

MW16

MW18

Data range: H0000 0000 to HFFFF FFFF

Soft-gate

M320

M328

Operation is enabled when ON

Note 1) The setting data range of the sampling time is 1 to 1000. (1 ms multiplier)

Note 2) When both the channels are configured in high speed mode, IP1 & IP2 cannot be used as normal input
devices. However, if either one channel is configured in high speed mode, the input of other channel can be used as
normal input device.

Hardware condition:

Count input (X000 and X001)

ON/OFF pulse width: 10 micro or more (max. 50 kHz)

Interrupt assignment:
No interrupt function