Toshiba Programmable Logic Controller V200 User Manual
Page 132
Page 124
No.
Event
Info1
Info 2
Info 3
Info 4
Special
Device
Meaning and
countermeasures
Check at
6
Scan
time over
Scan
time
MW01_2
MW02_1
The scan time has exceeded 200
mS (Default). (Alarm)Correct the
program to reduce the scan time
or use WDT instruction to extend
the check time.
Each main loop
scan
7
System
power off
Power OFF (no error)
Only Power-Up
8
System
power on
Power ON (no error)
Only Power-Up
9
WDT Error
MW01_00
MW01_11
The watchdog timer error has
occurred.(Error down) If the
error occurs frequently, replace
the unit.
Only Power-Up