Channel Type Selection Values Table:
Use the following values in the Input and output channel type select register to configure the corresponding channel
to particular type.
e.g. If you want to configure the Input channel 3 of GAD208**S model as ( 0 – 10 V ) type, then move value 19 in
MWxx16 configuration register. Here xx digital denotes the slot number in which the GAD208**S model is
connected to PLC. The Conversion Enable Flag should be one to start the conversion (A to D or D to A).
Input Channel Type
Value
Not Defined
0
mV( 0 - 100 mV )
1
mV( 0 - 50 mV )
3
mA( 0 - 20mA )
5
mA( 4 - 20mA )
7
Voltage ( 0 - 10V )
19
Voltage ( 1 - 5V )
20
RTD PT-100 (alpha1)
9
RTD PT-100 (alpha2)
10
RTD PT-1000
21
Thermocouple (B-Type)
11
Thermocouple (R-Type)
12
Thermocouple (S-Type)
13
Thermocouple (E-Type)
14
Thermocouple (J-Type)
15
Thermocouple (K-Type)
16
Thermocouple (N-Type)
17
Thermocouple (T-Type)
18
Output Channel Type
Value
Not Defined
0
mA( 4 - 20mA )
1
Voltage ( 0 - 10V )
2