• As a minimum, the installation of the equipment should conform to the NEC Article 110
Requirements For Electrical Installations, OSHA, as well as any other applicable
national, regional, or industry codes and standards.
• Installation practices should conform to the latest revision of NFPA 70E Electrical Safety
Requirements for Employee Workplaces.
Conductor Routing and Grounding
• Use separate metal conduits for routing the input power, and control circuits.
• A separate ground cable should be run inside the conduit with the input power, and
control circuits.
• DO NOT connect control terminal strip return marked CC to earth ground.
• Always ground the unit to prevent electrical shock and to help reduce electrical noise.
T h e M e t a l O f C o n d u i t I s N o t A n A c c e p t a b l e G r o u n d .