Toshiba Programmable Logic Controller V200 User Manual
Page 96
Page 88
PWM Output Function
Pulse Enable Flag (Device)
M336
Frequency Setting Register
MW22, MW23
ON duty setting register
MW24, MW25
pulse width error flag
M189
On duty setting error flag
M190
Frequency Setting Error Flag (Device)
M191
The Mode selection is done through two registers as below.
Configuration Register 10 (High Speed Input): ( MW0010).
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
0
0
0
0
Reserved
0: Variable input filter disable
1: Variable input filter enable
000: Normal
001: Ch2INT
010: Ch2HSC
011: Quadrature
100: Ch2 Single
phase counter
0: INT1 Rising
1: INT1 Falling
000: Normal
001: Ch1INT
010: Ch1HSC
011: Quadrature
100: Ch1 Single
phase counter
0: INT2 Rising
1: INT2 Falling
Channel1 HSC (Adding Counter)
0: Single Phase Up Counter
1: Single Phase Down Counter
Channel2 HSC (Adding Counter)
0: Single Phase Up Counter
1: Single Phase Down Counter
Quadrature
00: 1X mode
01: 2X mode
10: 4X Mode