3 devicenet configuration – Toshiba G7 User Manual
Page 25

G7 ASD Multi-Protocol Communication Option and PG Feedback Option Manual
18
8.3 DeviceNet Configuration
When parameter F890 is selected for DeviceNet communications, then the additional Network
Configuration Parameters are assigned the functions as indicated in Table 7.
Table 7: DeviceNet Network Configuration Parameters
Parameter Function
Settings
Default
Value
F891 Baud
Rate
0: 125kbaud
1: 250kbaud
2: 500kbaud
0
F892
Network
Communication
Loss Action
0 = Set all consumed data to 0
1 = Retain last data values
2 = Issue STOP command to drive
3 = Issue EMERGENCY OFF
command to drive
4 = Run preset speed #1
5 = Run preset speed #2
6 = Run preset speed #3
7 = Run preset speed #4
8 = Run preset speed #5
9 = Run preset speed #6
10 = Run preset speed #7
11 = Run preset speed #8
12 = Run preset speed #9
13 = Run preset speed #10
14 = Run preset speed #11
15 = Run preset speed #12
16 = Run preset speed #13
17 = Run preset speed #14
18 = Run preset speed #15
0
F893
Selected I/O
Assembly
Instance Set
0: Toshiba-specific
1: Basic speed control
2: Extended speed control
0
F894
Unused
N/A (Always 0)
0