JKSSS+ Series - 68

JKSSS+ Series

2.3 - 4.2KV

• Thermal Register Minimum: Sets the value

in the thermal register which represents a

motor running at the nameplate current (with

no overheating or negative sequence currents

present).

Motor Design Ambient Temperature: Use the

data from the motor manufacturer’s specifications.

When RTDs are used, this setpoint will be the

base point for the RTD biasing of the Thermal

Register.

• Motor Design Run Temperature: Use the data

from the motor manufacturer’s specifications. This

setpoint defines the operating temperature rise of

the motor at full load amps or 100% load.

• Motor Stator Max Temperature: This represents

the maximum temperature the stator insulation

will withstand. The user may choose to use

the temperature setting of the insulation class

(selected in Setpoint Page 1) or enter a specific

maximum temperature. This value should not

exceed the stator’s insulation temperature. This

maximum temperature represents 100% thermal

capacity.

• U/B Input to Thermal Register: Always enabled.

It allows the soft starter to use the line current

imbalance information to bias the Thermal

Register.

• User Calculated K or Assign: When the setpoint

is set to ON the controller will calculate the k

constant factor for biasing the thermal register, or

the user may choose to assign the k value.

SP12.4 Press Enter to CLR Thermal Register: Allows

the level three password user to clear the thermal

register for emergency restarts.

SP.12 System Setpoints (Setpoint Page 12)

(Security Level: 3)

SP12.1 Default Display Screen: This setpoint group

allows the user to choose the default screen the

soft starter displays while the motor is running.

Select the metering page number (1-3), then

select the metering screen number. The range

varies depending on the selected page. To display

a default screen, program the following two

setpoints:

• Metering Data Page#: Range is Page 1 - 3.

• Metering Data Screen#: If Page 1 is selected

as the default page, then Screens 1- 10 are

available. If Page 2, Screens 1-29 are available.

If Page 3 is selected, then Screens 1-6 are

available. (See Metering Menu, MP.1, for screen

number assignment.)

SP12.2 Alarms: Configures the RTD failure alarm and the

thermal register alarm.

• RTD Failure Alarm: If enabled, and an RTD

shorts or open, an alarm occurs.

• Thermal Register Alarm: Sets a level in the

thermal register to generate an alarm when the

Thermal Register Capacity Used has exceeded

this level.

• Thermal Alarm Delay: The amount of time that

the Thermal Register Used must exceed the

setpoint before an alarm condition will occur.

SP12.3 Thermal Register Setup Information: This

setpoint group will configure the thermal register

and indicate to the soft starter which inputs to use

when thermal modeling.

• Cold Stall Time: Enter the time from the motor

manufacturer’s specification sheet or use the time

defined by the OL Class. This setpoint is used to

define the thermal capacity of the motor.

• Hot Stall Time: Enter the amount of time

specified by the motor manufacturer or use half of

the time defined by the OL Class.

• Stopped Cool Down Time: The time the motor

requires to cool down after it has stopped. Use

only the data provided by the motor manufacturer.

This setpoint is used to configure the cooling rate

of the thermal register.

• Running Cool Down Time: The amount of

time the motor requires for cooling down while

running. Use only the data provided by the motor

manufacturer.

• Relay Measured Cool Rates: When RTDs are

used, the soft starter can be configured to use the

measured cool rates from the RTDs instead of the

programmed settings. This setpoint should only be

enabled when RTDs are present.