SP.4 Relay Assignment (Setpoint Page 4)

(Security Level: 2)

The protection functions are user programmable to an output relay. Factory setting for the trip functions assigned to TRIP

(AUX1) relay and alarm functions to ALARM (AUX2) relay. AUX1 - 4 are Factory Set and should not be changed.

SP4.1 The following is a list of the user programmable functions.

FUNCTIONS

RELAy ASSIGNMENTS

1st

2nd

3rd

OVERLOAD TRIP

TRIP ONLY

NONE

NONE

IMBALANCE TRIP

TRIP (AUX1)

NONE

NONE

SHORT CIRCUIT TRIP

TRIP ONLY

NONE

NONE

OVERCURRENT TRIP

TRIP (AUX1)

NONE

NONE

STATOR RTD TRIP

NONE

NONE

NONE

NON-STATOR RTD TRIP

NONE

NONE

NONE

GROUND FAULT HI SET TRIP*

TRIP (AUX1)

NONE

NONE

GROUND FAULT LO SET TRIP*

TRIP (AUX1)

NONE

NONE

PHASE LOSS TRIP

TRIP (AUX1)

NONE

NONE

ACCEL TIME TRIP

TRIP ONLY

NONE

NONE

START CURVE TRIP

TRIP ONLY

NONE

NONE

OVER FREQUENCY TRIP

NONE

NONE

NONE

UNDER FREQUENCY TRIP

TRIP (AUX1)

NONE

NONE

I*I*T START CURVE

TRIP (AUX1)

NONE

NONE

LEARNED START CURVE

TRIP (AUX1)

NONE

NONE

PHASE REVERSAL

TRIP (AUX1)

NONE

NONE

OVERVOLTAGE TRIP

TRIP (AUX1)

NONE

NONE

UNDERVOLTAGE TRIP

TRIP (AUX1)

NONE

NONE

POWER FACTOR TRIP

NONE

NONE

NONE

TACH ACCEL TRIP

NONE

NONE

NONE

INHIBITS TRIP

TRIP (AUX1)

NONE

NONE

SHNT TRIP

NONE

NONE

NONE

BYPASS DISCREPANCY

NONE

NONE

NONE

TCB FAULT

TRIP (AUX1)

NONE

NONE

EXTERNAL INPUT 2

NONE

NONE

NONE

DUAL RAMP

NONE

NONE

NONE

THERMOSTAT

TRIP (AUX1)

NONE

NONE

OVERLOAD WARNING

ALARM (AUX2)

NONE

NONE

OVERCURRENT ALARM

ALARM (AUX2)

NONE

NONE

SCR FAIL SHUNT ALARM

ALARM (AUX2)

NONE

NONE

GROUND FAULT ALARM*

ALARM (AUX2)

NONE

NONE

UNDERCURRENT ALARM

NONE

NONE

NONE

MOTOR RUNNING

AUX3

NONE

NONE

IMBALANCE ALARM

ALARM (AUX2)

NONE

NONE

STATOR RTD ALARM

NONE

NONE

NONE

NON-STATOR RTD ALARM

NONE

NONE

NONE

RTD FAILURE ALARM

NONE

NONE

NONE

SELF TEST FAIL

TRIP (AUX1)

NONE

NONE

THERMAL REGISTER

ALARM (AUX2)

NONE

NONE

U/V ALARM

ALARM (AUX2)

NONE

NONE

O/V ALARM

ALARM (AUX2)

NONE

NONE

POWER FACTOR ALARM

NONE

NONE

NONE

KW DEMAND ALARM

NONE

NONE

NONE

KVA DEMAND ALARM

NONE

NONE

NONE

KVAR DEMAND ALARM

NONE

NONE

NONE

AMPS DEMAND ALARM

NONE

NONE

NONE

TIMED OUTPUT

NONE

NONE

NONE

RUN DELAY TIME

NONE

NONE

NONE

AT SPEED

AUX4

NONE

NONE

*Ground fault option must be installed.