Jksss+ series 2.3 - 4.2kv – Toshiba VF010H05 User Manual
Page 27
JKSSS+ Series - 21
JKSSS+ Series
2.3 - 4.2KV
Controller used as service equipment for an ungrounded system or as a main section for a separately derived
system.
a. A grounding electrode conductor (ground wire) sized in accordance with NEC 250 should be run from the
grounding electrode to the controller ground bus or ground terminal.
b. If the system is grounded at any point ahead of the controller, the grounded conductor should be run to the
controller in accordance with NEC 250 and connected to the ground bus or ground terminal.
c. Steps (a) and (b) should effectively connect together the grounding electrode, the controller frame, all outgoing
equipment grounding connectors and any grounded conductor which runs to the controller.
Controller not used as service equipment or as a main section for a separately derived system, and used on either
a grounded or ungrounded system:
a. The controller frame and any ground bus should be grounded by means of equipment grounding conductors
having a size in accordance with NEC 250 and run with the main supply conductors or by bonding to the
raceway enclosing the main supply conductors in accordance with NEC 250.
b. Ground leads should be connected to cable potheads/shields as specified by the manufacturer of these de-
vices.
Fig. 7 Ground Bus Splice