beautypg.com

Jksss+ series 2.3 - 4.2kv, Menu – Toshiba VF010H05 User Manual

Page 69

background image

JKSSS+ Series - 63

JKSSS+ Series

2.3 - 4.2KV

SP.9 RTD Optional Configuration (Setpoint Page 9)

(Security Level: 3)

MENU

PAGE 9 RTD
CONFIGURATION

USE NEMA TEMP FOR
RTD VALUES: DISABLED

(Hit DOWN ARROW eight times)

Options: ENABLED OR

DISABLED

# OF RTD’S USED FOR
STATOR: 4

RTD VOTING
: DISABLED

STATOR PHASE A2 TYPE
: OFF

STATOR PHASE B1 TYPE
: OFF

STATOR PHASE B2 TYPE
: OFF

STATOR PHASE A1 TYPE
: OFF

STATOR PHASE C1 TYPE
: OFF

Range: 0 - 6
Increments of 1

Options: ENABLED or
DISABLED

Range: *

Range: *

Range: *

Range: *

Range: *

RTD # 2 DESCRIPTION
STATOR PHASE A2

RTD # 3 DESCRIPTION
STATOR PHASE B1

RTD # 4 DESCRIPTION
STATOR PHASE B2

RTD # 1 DESCRIPTION
STATOR PHASE A1

RTD # 5 DESCRIPTION
STATOR PHASE C1

Range: ***

Range: ***

Range: ***

Range: ***

Range: ***

STATOR PHASE A2 ALARM
LEVEL: OFF

STATOR PHASE B1 ALARM
LEVEL: OFF

STATOR PHASE B2 ALARM
LEVEL: OFF

STATOR PHASE A1 ALARM
LEVEL: OFF

STATOR PHASE C1 ALARM
LEVEL: OFF

Range: **

Range: **

Range: **

Range: **

Range: ***

STATOR PHASE A2 TRIP
LEVEL: OFF

STATOR PHASE B1 TRIP
LEVEL: OFF

STATOR PHASE B2 TRIP
LEVEL: OFF

STATOR PHASE A1 TRIP
LEVEL: OFF

STATOR PHASE C1 TRIP
LEVEL: OFF

Range: **

Range: **

Range: **

Range: **

Range: ***

END BEARING TYPE
: OFF

SHAFT BEARING TYPE
: OFF

RTD # 9 TYPE
: OFF

STATOR PHASE C2 TYPE
: OFF

RTD # 10 TYPE
: OFF

Range: *

Range: *

Range: *

Range:*

Range: *

RTD #7 DESCRIPTION
END BEARING

RTD # 8 DESCRIPTION
SHAFT BEARING

RTD # 9 DESCRIPTION
RTD # 9

RTD # 6 DESCRIPTION
STATOR PHASE C2

RTD # 10 DESCRIPTION
RTD # 10

Range: ***

Range: ***

Range: ***

Range: ***

Range: ***

END BEARING ALARM
LEVEL: OFF

SHAFT BEARING ALARM
LEVEL: OFF

RTD # 9 ALARM
LEVEL: OFF

STATOR PHASE C2 ALARM
LEVEL: OFF

RTD # 10 ALARM
LEVEL: OFF

Range: **

Range: **

Range: **

Range: **

Range: **

END BEARING TRIP
LEVEL: OFF

SHAFT BEARING TRIP
LEVEL: OFF

RTD # 9 TRIP
LEVEL: OFF

STATOR PHASE C2 TRIP
LEVEL: OFF

RTD # 10 TRIP
LEVEL: OFF

Range: **

Range: **

Range: **

Range: **

Range: **

RTD # 11 TYPE
: OFF

RTD # 12 TYPE
: OFF

Range: *

Range: *

RTD # 11 DESCRIPTION
RTD #11

RTD # 12 DESCRIPTION
RTD # 12

Range: ***

Range: ***

RTD # 11 ALARM
LEVEL: OFF

RTD # 12 ALARM
LEVEL: OFF

Range: **

Range: **

RTD # 11 TRIP
LEVEL: OFF

RTD # 12 TRIP
LEVEL: OFF

Range: **

Range: **

Ranges:

*

**

***

120 OHM NICKEL (NI)

100 OHM NICKEL (NI)
10 OHM COPPER (CU)
100 OHM PLATINUM (PT)
OFF

OFF or 0 - 240C (32-464F) Example: ### C = ### F

Increments of 1

STATOR A1, STATOR A2, STATOR B1, STATOR B2, STATOR C1, STATOR C2,

FRONT BEARING, BACK BEARING, BEARING BOX, AMBIENT, NONE